GUIDE SPECIFICATIONS
GENERAL
Sy st em Descripti o n
Outdoor-- mounted, air--cooled, split--system air conditioner unit
suitableforground orrooftop installation.Unit consistsofahermetic
compressor, an air--cooled coil, propeller--type condenser fan, and a
control box. Unit will discharge supply air upward as shown on
contractdrawings.Unit will beused in a refrigeration circuit to match
up to a packaged fan coil or coil unit.
Quality Assurance
Unit will be rated in accordance with the latest e dition of
ARI Standard 210.
Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
Unit c onstruction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have c--UL approval.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
Air--cooled condenser coils will be leak tested and
pressure tested.
Unit constructed in ISO9001 approved facility .
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclu si o n by speci fy i n g engi n eer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled air
conditioner unit. Contained within the unit enclosure is
all factory wiring, piping, controls, compressor,
refrigerant charge Puronr (R --410A), and special features
required prior to field start--up.
Unit Cabinet
Unit cabinet, including louvered coil guard, will be
constructed of galvanized steel, bonderized, and coated
with a powder coat paint.
Fans
Condenser fan will be direct--drive propeller type,
discharging air upward.
AIR--COOLED, SPLIT --SYSTEM AIR CONDITIONER
124A
1 --1 /2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed, 1 --phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration
isolators.
Compressor will be covered with a sound absorbing
blanket.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigera ti on Compo n en ts
Refrigeration circuit components will include liquid--line
shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puronr
(R--410A) refrigerant, and compressor oil.
Unit will be equipped with high --pressure switch, low
pressure switch and filter drier for Puron refrigerant.
Op erati n g Chara cteri sti cs
The capacity of the unit will meet or exceed _____ Btuh
at a suction temperature of _____ _F/_C. The power
consumption at full l oad will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F/_C wet bulb
and _____ _F/_C dry bulb, and air entering the unit at
_____ _F/_C.
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
El ectri ca l Requ i rements
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Sp eci a l Featu res
Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
Manufacturer reserves theright to discontinue, or changeat any time, s pecifications or designs without notice and without i ncurring obligations.
E 2009 BryantHeating & Coo ling Systems 7310 W. MorrisSt. Indianapolis, IN 46231 Printed i n U.S.A. Edition Date: 02/09
Replaces: PDS124A---06
Catalog No. PDS124A--- 07
124A