7.7 Keypad Error Displays
7.7.1 General Information
Display Meaning
DS7445/DS7445i:
Power LED flashing
DS7447/DS7447E:
Control Trouble Enter #87
There is an Error Message. To
display the message, enter [PIN] + [#
]
[8] [7].
DS7445/DS7445i:
LED 1 On
DS7447/DS7447E:
AC Power Failure
There is a power failure, and the
panel is operating on backup battery
power.
DS7445/DS7445i:
LED 2 On
DS7447/DS7447E:
Battery Trouble*
If the system has just been through a
power failure, wait at least two hours
for the battery to recharge, the enter
[PIN] + [System Reset] to perform a
battery test,
DS7445/DS7445i:
LED 3 On
DS7447/DS7447E:
Communicator Err**
The communicator failed to
communicate with the Central
Station.
DS7445/DS7445i:
LED 4 On
DS7447/DS7447E:
System Fault
Internal error in the control circuitry or
optional circuitry. See System Faults.
DS7445/DS7445i:
LED 5 On
DS7447/DS7447E:
Keypad Fault
One of the keypads is not responding
to the Control Panel.
DS7445/DS7445i:
LED 6 On
DS7447/DS7447E:
Keypad Tamper
One of the keypad housings has
been opened.
DS7445/DS7445i:
LED 7 On
DS7447/DS7447E:
Multiplex Bus
The multiplex bus is defective or has
been shorted.
DS7445/DS7445i:
LED 8 On
DS7447/DS7447E:
Aux. Power Fault
The auxiliary power has been
shorted.
DS7445/DS7445i:
not applicable
DS7447/DS7447E:
Zone Trouble
One of the zones is not responding to
the Control Panel. This may also be
displayed during power-up; if so,
ignore it.
DS7445/DS7445i:
not applicable
DS7447/DS7447E:
RF
Indicates a problem with an RF
(wireless) zone.
DS7445/DS7445i:
not applicable
DS7447/DS7447E:
Dirty Chamber
One of the multiplex smoke detectors
has failed the sensitivity test and may
require cleaning or replacement. The
keypad beep may be cleared by
entering [PIN] + [Off].
Error Displays can only be read when the control is disarmed.
Some Control Panel Errors, such as battery trouble and any RF
troubles, will cause the keypad sounders to beep every 10 seconds.
The keypad sounders may be silenced for 4 hours by entering:
[PIN] + [Off].
The sounders will continue to resound until the problem is fixed.
To Clear a display, enter:
[PIN] + [System Reset].
Clear the Error Display only on the advice of your
installing company or if you are certain the problem
has been remedied.
NOTE: System faults may be read from any keypad because they
are system-wide. All other Error Displays are limited to
the partition the standard keypad is in. If you are on a
Master keypad, you may read Error Displays one partition
at a time.
7.7.2 System Faults
System faults are designated as follows:
[#] [8] [7] will display [#] [8] [9] will
display
RAM Fault System Fault 01
ROM Fault System Fault 02
EEPROM Fault System Fault 03
Ground Fault System Fault 04
2Ph/Bell Fault = loss of communication to
DS7420i
System Fault 10
Line 1 Fault = DS7420I phone line 1 fault System Fault 11
Line 2 Fault = DS7420I phone line 2 fault System Fault 12
Bell Fault = DS7420i bell circuit fault System Fault 13
Aux. Relay Fault = DS7420I auxiliary relay
fault
System Fault 14
Oct. Relay Fault = loss of communication to
DS7488
System Fault 20
Reserved for older panels System Fault 50
AR IB Queue Full = modem buffer full System Fault 51
AR Host Down = network data switch down System Fault 52
AR Unreg. Modem = modem not registered System Fault 53
AR Power Fail = power source below
defined threshold
System Fault 54
AR Network Lost = loss of network System Fault 55
AR Modem HW Err = modem hardware
error
System Fault 56
AR Modem SW Err = modem software
error
System Fault 57
AR Opt. Bus Err = loss of communications
to ARDIS module
System Fault 58
AR Corrupt MSG = message error System Fault 59
7.7.3 Event History
The History Buffer stores the last 400 events in memory. The
DS7447/DS7447E can display all of these events. If this test is
performed from a Master keypad, it must be in Single Partition
Mode. The DS7445/DS7445i will only display those zones (1-8)
that have alarmed since the last Event History Readback. The
RF3341 cannot display history events.
To readback the Event History Buffer:
Press [PIN] + [#] [8] [9]. On a DS7447/DS7447E keypad, the last
event to take place will be displayed. On a DS7445/DS7445i
keypad, the zone LEDs for any zones that have alarmed since
the last Event History Readback in that partition will flash.
Scroll through the events using the [9], [6], and [#] keys as follows:
To begin scrolling back through the events, press the [#] key. The
[#] key will scroll you back through the history line by line. The [9]
key will scroll you back in reverse chronological order by event. A
[6] will scroll you back up through the events (toward the most
recent) by event.
Each event consists of two or three lines or display screens. The
first line/screen will be the event title and user. The second line/
screen will be the date of the event or the change being made. If
there is a third line/screen, it will be the date of the change.
NOTE: When performing this from a Master keypad, each partition
will display its own history.
To exit the Event History Mode, press the [*] key or wait 20 seconds
and the keypad will exit automatically.