Bosch Appliances D9412GV3 Home Security System User Manual


 
D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0 Off-Board Points
.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 42
Figure 18: Program Record Sheet
9.3.8 POPIT Labels
D9412GV3 off-board points are numbered 9 to 127
and 129 to 247. The D7412GV3 uses Points 9 to 75
only. The D9412GV3 reserves Points 128 and 248 for
internal use. POPITs must be connected for Points
129 to 247 to expansion loops connected to POPEX
#2.
Two sheets of peel-off POPIT labels are supplied with
the D8125 POPEX Module. Use the sheet marked
“Bank1” for Points 9 to 127. Use the sheet marked
“Bank2” for Points 129 to 247.
Each label has two parts. Place the smaller part (with
only the point number) on the chip. Place the larger
part with the switch settings on the base of the
POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point
number. After programming all the points, perform a
Service Walk Test. Refer to Section 4.10 Service
Walk Test on page 44. If a point does not test, check
the programming for a duplicated address.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, missing and
extra points can occur. If the same point number is
assigned to two or more POPITs or OctoPOPITs,
none of the points with that number test correctly.
Refer to Section 9.1 Point (Zonex) Bus: D9412GV3
Terminals and D7412GV3 Terminals on page 36.
For UL 864 Commercial Fire applications,
refer to Installing Combination Fire and
Intrusion Alarm Systems in the
D9412GV3/D7412GV3 Approved
Applications Compliance Guide
(P/N: F01U143069) for important
information about combination fire and
intrusion systems.
9.4 D8128D OctoPOPIT Module
Modules D8128, D8128A, or D8128B are
incompatible with the D9412GV3 or
D7412GV3. Use only the D8128D
OctoPOPIT Module. Using Modules
D8128, D8128A, or D8128B can cause
intermittent Missing and Restoral Reports.
9.4.1 Description
The D8128D OctoPOPIT Module combines the
functions of the D8125 POPEX Module and the
D9127 POPIT Modules to provide eight off-board
points in a single module. You can wire both D8128D
OctoPOPIT and D8125 POPEX Modules in parallel to
the Zonex Bus terminals on the same control panel.
Review Section 6.0 Power Outputs on page 26 to
ensure that there is enough power for the
OctoPOPITs and other powered devices that will be
connected to the system.
Up to thirty D8128D Modules can be connected to the
D9412GV3 Control Panel. Up to nine D8128Ds can
be connected to the D7412GV3 Control Panel (three
points can be used on the last OctoPOPIT).