Bosch Appliances D7412G Home Security System User Manual


 
D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS EN | 82
Bosch Security Systems | 1/04 | 47775E
P## Pt Response
Default: See
Program Record Sheet
Selection: 0 to F
Controlled (Non-24-Hour Points)
Point Response 0123456789ABCDEF
Armed Open
IIIIDDIIDIIIIIT
Armed Short
IIIIIIDDDIIIIII
Disarmed Open
TT TIITIT
Disarmed Short
TT T ITI I
24-Hour Points
Point Response 0123456789ABCDEF
Open ITIT ITSTS S
Short I I T T I T T S S S
Key: I = Instant alarm
D = Delayed alarm
T = Trouble
S = Supervisory
Blank = Audible/visual response
Example of Controlled point:
Point Type = 1
Point Response = 8
Perimeter point with delayed alarm response when
armed (opened or shorted) and no response when
disarmed.
Example of 24-hour point:
Point Type = 0
Point Response = 8
24-hour point with supervisory response when open
and a trouble response when shorted.
0101
0101
0101
When programming the point response
for Inovonics Wireless Transmitters,
regardless of how the transmitter is
programmed, the D8125INV Wireless
Interface always sends the off-normal
state to the control panel as a short and a
tamper condition as an open. As a result,
typical point responses for the Inovonics
transmitters would include 0, 1, 6, 7, and
E for Controlled points, and 0 and 1 for
24-hour Burg points. When programming
a transmitter as a Fire point, a Point
Response of 1 is recommended.
Note:
Wireless transmitters are NOT UL Listed with
the D9412G/D7412G in fire or burglary
applications. At present, Inovonics Wireless
Transmitters, when used with the D8125INV
Wireless Interface on a 9000 Series Control
Panel, are not UL Listed for use with fire or
burglary applications.
With Supervisory Pt Response (S =
Supervisory), the BFSK format does not
transmit fire supervisory or Non-fire
Supervisory Events. Modem format must
be used with Supervisory Point
Responses.