Bosch Appliances D1256RB Smoke Alarm User Manual


 
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
12 Bosch Security Systems, Inc. | 8/06 | F01U011791B
4.4.5 Keypad (Command Center) Functions
The following keypad function must be enabled or
passcode required to enable the [DETECTOR RESET]
key.
#27 Reset Sensors
Include the following items in the menu:
#9 View Event Memory
#10 View Point Status
#12 Fire Test
#21 View Log
#29 Remote Program
#32 Display Rev
Refer to Figure 18.
For the D9412GV2 Control Panel, program
each of the keypad functions with E
(enabled) and not P (passcode required). If
restricting any of the keypad functions with
a passcode is required, those functions
must be executed from a custom function
that includes an authorized passcode.
Example (Refer to Figure 18.): If the
keypad function View Memory is
programmed as P (passcode required), and
the passcode 125600 has authority to
execute it, the keystrokes would be:
[A] [4] [0] [1] [2] [5] [6] [0] [0] [E]
When creating a Menu Function List for a
keypad address, consider that the
D1256RB Keypad does not have numeric
keys. Ensure that:
no passcode-protected keypad functions
are in a Menu Function List enabled at
an address that coincides with the
installed address for a D1256RB
Keypad.
the
CC# Menu Key Lock
prompt is set
to No for the D1256RB address.
Figure 18: Example – Keypad Functions
Keypad Functions
# Functions Command
E/P*
1 Disarm ?
P
2 Master Arm Delay ? CMD 1
P
3 Master Arm Instant ? CMD 11
4 Perimeter Instant ? CMD 2
P
5 Perimeter Delay ? CMD 3
P
6 Watch Mode ? CMD 6
E
7 Perimeter Part ? CMD 8
P
8 View Area Status ?
P
9 View Memory ? CMD 40
E
10 View Pt Status ?
E
11 Walk Test ? CMD 44
E
12 Fire Test ? CMD 58
P
13 Send Report ? CMD 41/42
P
14 Door Control ? CMD 46
P
Cycle Door ?
E
Unlock Door ?
E
Secure Door ?
E
37 Access Control Level?
P
15 Change Display ? CMD 49
E
16 Change Time/Date ? CMD 45
E
17 Change Passcode ? CMD 55
P
18 Add User ? CMD 56
P
19 Del User ? CMD 53
P
20 Extend Close ? CMD 51
P
21 View Log ?
E
22 Print Log ?
P
23 User Command 7 ? CMD 7
P
24 User Command 9 ? CMD 9
P
25 Bypass a Point ? CMD 0
P
26 Unbypass a Point ? CMD 00
P
27 Reset Sensors ? CMD 47
E
28 Change Relays ? CMD 54
P
29 Remote Program ? CMD 43
P
30 Move To Area ? CMD 50
P
32 Display Rev ? CMD 59
E
33 Service Walk ?
P
34 Default Text ? CMD 57
P
35 Change Skeds ? CMD 52
P
36 Invisible Walk ?
P
* Keypad Function options: P = Passcode;
E = Enabled (no passcode required);
Blank = Disabled