Berkley B2XRKS Water Pump User Manual


 
Page 12 F00633
Discharge Connection
Installation
Use Concentric Reducer
to mimimize friction losses.
Isolation
Valve
Support piping
as required
Non-Slam or
spring loaded
check valve.
Isolation valve to
permit servicing of
check valve or pump.
Align piping to
minimize flange
stress.
Pressure
Gauge
Discharge pipe diameter
at least one nominal pipe
size larger than discharge
opening in pump.
2118 1195
Recommended
Use pipe, tubing or reinforced hose to make dis-
charge connection. Material selected must have
sufficient strength for operating pressures.
Discharge pipe should be sized so that flow velocity is
below 8 feet per second.
Use ONLY non-slamming check valves to prevent
hydraulic shock (water hammer).
Use gate, ball, or butterfly valve for isolation. Valve
should be full open during operation.
Maintain proper pipe size throughout discharge
system, using as few elbows and tees as possible to
keep friction loss to a minimum.
Install pressure gauge after reducer as shown to
check operating pressure or shut-off head.