Bard CH3S1 Heat Pump User Manual


 
Manual 2100-455M
Page 4 of 28
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
CH 4S 1 – A 05 B P X X X X
TABLE 1
ELECTRIC HEAT TABLE
Models
KW
CH
3S1-A CH3S1-B CH3S1-C
CH4S1-A
CH5S1-A
CH4S1-A
CH5S1-A
CH4S1-A
CH5S1-A
240-1 208-1 240-3 208-3 460-3 240-1 208-1 240-3 208-3 460-3
A BTU A BTU A BTU A BTU A BTU A BTU A BTU A BTU A BTU A BTU
4 16.7 13650 14.4 10240
5 20.8 17065 18.1 12800 20.8 17065 18.1 12800
6 14.4 20500 12.5 15360 7.2 20480 14.4 20500 12.5 15360 7.2 20480
9 21.7 30600 18.7 23030 10.8 30700 21.7 30600 18.7 23030 10.8 30700
10 41.6 34130 36.2 25600 41.6 34130 36.2 25600
15 62.5 51200 54.1 38400 36.2 51200 31.2 38400 18 51200 62.5 51200 54.1 38400 36.2 51200 31.2 38400 18 51200
18 43.3 61400 37.5 46050 21.6 61400
20 83.2 68250 72.1 51200
MODEL NUMBER
CONTROL MODULES
CAPACITY
3S - 3 ton
4S - 4 ton
5S - 5 ton
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
REVISIONS
KW
VENTILATION OPTIONS
B - Blank-off Plate
R - Energy Recovery
V - Commercial Ventilator -
Motorized with Exhaust
FILTER OPTIONS
P - 2-Inch Pleated
COLOR OPTIONS
X - Beige (Standard)
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
COIL OPTIONS
X - Standard
OUTLET OPTIONS
X - Front (Standard)
T - Top Outlet