Avalon Stoves Indoor Fireplace Indoor Fireplace User Manual


 
12 Installation
Travis Industries 4050525 100-01144
Mobile Home Requirements
Outside air is required (used for combustion) - see the directions below.
WARNING: DO NOT INSTALL IN SLEEPING ROOM.
CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME
FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.
Outside Air (used for combustion)
Outside air is optional (except in mobile homes or when required by local building codes).
Must not be drawn from an enclosed space (garage, unventilated crawl space).
Must not be over 15' long.
Must be made with 1 3/4" diameter or larger metal or aluminum duct with a metal screen
attached to the end to keep out rodents (P.V.C. or other combustible materials may not
be used). Use the Travis Industries Outside Air Kit (part # 99200136).
Must not terminate above or within 1' of the chimney termination.
Must have a rain cap or down-turned elbow to prevent water from entering.
Must be located so that it will not become plugged by snow or other material.
Vent Termination
12 Min.
Outside air may be drawn
through the chimney (15
maximum length).
Outside air may be drawn
from the ash cleanout.