AquaStar 38B NG Water Heater User Manual


 
GAS LINE SIZE
Natural Gas
Nominal Iron Pipe Size* 3/8" 1/2"
MAXIMUM LENGTH
20' 80'
Liquid Propane
Semi-rigid Tubing 3/8" 1/2"
MAXIMUM LENGTH
10' 60'
* Flex tubing greatly reduces capacity and, therefore, is not recommended.
Minimum Vent Size* and Height
Minimum Diameter Minimum Height**
4 inches 6 feet**
* NOTE
: Vent size must not be restricted. Installation must comply with national fuel
g
as code ventin
g
requirements
for a 40,000 Btu Cate
g
ory I appliance and any applicable local codes.
Water Pressure
For installation on well systems, insure that your water pressure is between 30 - 50 psi.
** NOTE
: 6 feet, provided there are no elbows. Termination of vent must be 2 feet above any obstruction within a
10 foot radius. Consult your
g
as utility or National Fuel Gas Code if vent will have elbows or share ventin
g
with
another appliance. The vent connector should have as much vertical rise as possible (minimum 12") before any
horizontal run.