APC ACRD101 Fan User Manual


 
InRow RD 10 kW Air Cooled Operation and Maintenance32
Network Management Card
Quick Configuration
The cooling unit is shipped with a Network Management Card that enables the cooling unit to be
managed over a network. Configure the Network Management Card to control this cooling unit through
a network.
Overview
You must configure the following TCP/IP settings before the Network Management Card can operate on
a network:
IP address of the Network Management Card
Subnet mask
Default gateway
Caution: Never use the loopback address (127.0.0.1) as the default gateway address
for the Network Management Card. Doing so will disable the card and will require you
to reset TCP/IP settings to their defaults using a local serial login.
Note: If a default gateway is unavailable, use the IP address of a computer that is
located on the same subnet as the Network Management Card and that is usually
running. The Network Management Card uses the default gateway to test the network
when traffic is very light.
See “Watchdog Features” in the “Introduction” of the User’s Guide for more
information about the watchdog role of the default gateway.
TCP/IP configuration methods
Use one of the following methods to define the basic TCP/IP settings needed by the Network
Management Card:
APC Device IP Configuration Wizard (See “APC Device IP Configuration Wizard” on this page.)
BOOTP or DHCP server (See “BOOTP & DHCP configuration” on page 33.)
Networked computer (See “Remote access to the control console” on page 35.)