Allied Air Enterprises A93DF Furnace User Manual


 
506725-01 Page 19 of 48
Issue 1109
FIGURE 23
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL
IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated sot
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
Clearance to unventilated sot
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
* 12"
* Equal to or greater than sot depth.
*
* 3 feet (.9m)
* 12"
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, N atural Gas and Pr opane Inst allation Code
between two single family dwellings and serves both dwellings.
sides beneath the oor. Lennox recommends avoiding this location if possible.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
* Equal to or greater than sot depth.
* Equal to or greater than sot depth.
* Equal to or greater than sot depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*For clearances not specied in ANSI Z223.1/NFPA 54 or CSA B149.1,
clearance will be in accordance with local installation codes and the re-
quirements of the gas supplier and these installation instructions."
**