Allied Air Enterprises A80UH2V Furnace User Manual


 
506471-01 Page 23 of 41Issue 1034
Gas Supply
1. This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applica-tions). Connect the gas supply to the piping
assembly.
2. When connecting the gas supply piping, consider factors
such as length of run, number of fittings, and furnace
rating to avoid excessive pressure drop. Table 9 lists
recommended pipe sizes for typical applications.
3. The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
NOTE: If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect main power to the furnace.
The installer should properly label these devices.
4. The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the furnace.
The piping must be supported at proper intervals [every
8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or
straps. Install a drip leg in vertical pipe runs to the unit.
5. A 1/8" N.P.T. plugged tap or pressure post is located on
the gas valve to facilitate test gauge connection. See
Figure 38.
6. In some localities, codes may require the installation of
a manual main shut off valve and union (furnished by
the installer) external to the unit. The union must be of
the ground joint type.
Gas Piping
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquified petroleum gases.
IMPORTANT
If a flexible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The flexible connector can then be added
between the black iron pipe and the gas supply line.
CAUTION
Table 9
Gas Pipe Capacity - ft³/hr (m³/hr)
Note: Capacity given in cubic feet (m³) of gas per hour and based on 06.0 specific gravity gas.