1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
685 Total Flt Al-
lowed
Total Faults Allowed Settings C&C 10 Changeable Service
686 Flt Dis Time Fault Disable Time Settings C&C 10 Changeable Service
693 Invert Rmt
SDown
Remoted Shutdown Inverted Logic
- Non-volatile conguration. Default from fac-
tory is Normally Open
Settings C&C Normally Open Nonchangeable
Changeable
Changeable
User
Administrator
Service
694 Reset HW
Fault
Reset Hardware Fault Latch Settings C&C 0 Changeable Service
695 Restart Mode* Restart UPS Mode
- Non-volatile conguration. Default from fac-
tory is On-Line
Settings C&C On-Line Nonchangeable
Changeable
Changeable
User
Administrator
Service
696 SWMishap
Mrstrt
Software Mishap restart mode Settings C&C 1 Changeable Service
697 Special
Purpose
(Call Factory for Further Information) Settings C&C Changeable
Changeable
Administrator
Service
701 System Op
Time
Total System Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
702 Inverter Op
Time
Total Inverter Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
703 Backup Op
Time
Total Backup Operation Time
- Non-volatile history record. Default from fac-
tory is zero.
Settings HIST 123 Sec Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
704 UPS Lifetime UPS Lifetime Remaining Time
- Non-volatile history record. Default from fac-
tory is 61320 Hour
Settings HIST 61320 Hr Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
705 Hi System
Temp
Highest System Temperature Recorded
- Non-volatile history record. Default from fac-
tory is 0 C.
Settings HIST 0 C Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
706 Hi Battery
Temp
Highest Ambient Temperature Recorded
- Non-volatile history record. Default from fac-
tory is -15 C.
Settings HIST -15 Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service