1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
442 DCUB SW
DeDelay
DCUB Detection Delay Setting DC 2 Changeable Service
504 Battery Capac-
ity
Battery Capacity Setting BATT 0 Nonchangeable
Changeable
Changeable
User
Administrator
Service
507 Total Discharg-
es
Number of Battery Discharges
- Increment count by one after UPS in Backup
mode for 10 seconds
Settings BATT 123 Nonchangeable
Changeable
Changeable
User
Administrator
Service
509 Batt Life Re-
main
Battery Lifetime Remaining Settings BATT 43800 Hr Nonchangeable
Changeable
Changeable
User
Administrator
Service
511 Rated Ahr* Rated Battery Ampere Hour
- One of the battery’s properties
Settings BATT 9 AHr Nonchangeable
Changeable
Changeable
User
Administrator
Service
512 No
Batt(Series)*
Number of Battery in Series Settings BATT 18 Nonchangeable
Changeable
Changeable
User
Administrator
Service
513 No Batt(Paral)* Number of Battery in Parallel Settings BATT 1 Nonchangeable
Changeable
Changeable
User
Administrator
Service
514 Batt Ins Date Battery installation Date
- YYYY/MM/DD format
Settings BATT 2008/01/01 Nonchangeable
Changeable
Changeable
User
Administrator
Service
516 Batt SDown
Level*
Battery Shutdown Level
- Percentage setting for shutdown level calcu-
lated. Actual shutdown level might be different
depends on the rate of discharge
Settings BATT 79 % Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
524 SbatEx External Battery Status Settings BATT Disable Nonchangeable
Changeable
Changeable
User
Administrator
Service
525 Ex # Batt
(Series)
Number of External Battery in Series Settings BATT 18 Nonchangeable
Changeable
Changeable
User
Administrator
Service
526 Ex # Batt
(Parallel)
Number of External Battery in Parallel Settings BATT 1 Nonchangeable
Changeable
Changeable
User
Administrator
Service