1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
655 Batt Test Freq* Max Battery Test Frequency
- Non-volatile conguration. Default from fac-
tory is Monthly.
Settings C&C Monthly Nonchangeable
Changeable
Changeable
User
Administrator
Service
656 Sys. Temp.
Comp.
System Temperature Compensation Settings C&C -5 Changeable Service
657 Service Port
Mode
Service Port Mode - Terminal or TUPS 2.0 Settings C&C 1 Changeable Service
658 En Restart Enable Restart
- Non-volatile conguration. After shutdown by
battery, UPS will restart if input power recover.
Default from factory is Enable.
Settings C&C Enable Nonchangeable
Changeable
Changeable
User
Administrator
Service
659 Restart Delay Restart Delay Settings C&C 10 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
660 En AutoXfer Enable Auto Transfer
- Non-volatile conguration. Enable auto
transfer when current limit occurs. It will switch
bypass and On-Line mode.
Settings C&C Enable Nonchangeable
Changeable
Changeable
User
Administrator
Service
662 AutoXfer Win-
dow
Auto Transfer Time Window
- Non-volatile conguration. Default from fac-
tory is 3 Seconds.
Settings C&C 3 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
663 Srv Port Baud* Service Port Baud Rate
- Non-volatile conguration. Default from fac-
tory is 57600.
Settings C&C 57600 Nonchangeable
Changeable
Changeable
User
Administrator
Service
680 Reload All EE* Reload all EEPROM Settings C&C 0 Changeable Service
681 SNMP Port
Mode
SNMP Port Mode: Terminal or Toshiba 2.0 Settings C&C 1 Changeable Service
682 Special
Purpose
(Call Factory for Further Information) Settings C&C Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
683 Flt Clear Mask
Lo
Fault Clear Mask Low Settings C&C 0x0000 Changeable Service
684 Flt Clear Mask
Hi
Fault Clear Mask High Settings C&C 0x0000 Changeable Service