FX Series Programmable Controllers Devices in Detail 4
4-13
4.6.3 Disabling Individual Interrupts
Individual interrupt devices can be temporaril
or permanentl
disabled b
drivin
an
associated special auxiliar
rela
. The relevant coils are identified in the tables of devices in
chapter 6. However for all PLC t
pes the head address is M8050, this will disable interrupt
I0 .
Driving special auxiliary relays:
• Never drive a special auxiliar
coil without first checkin
its use. Not all PLC’s assi
n the
same use to the same auxiliar
coils.
Disabling high speed counter interrupts
• These interrupts can onl
be disabled as a sin
le
roup b
drivin
M8059 ON.
Further details about counter interrupts can be found in the followin
section.
4.6.4 Counter Interrupts
Identification of interrupt pointer number:
Example:
The sequence pro
rammed after the label
(indicated b
the I030 pointer) is executed once
the value of Hi
h Speed Counter C255
reaches/equals the preset limit of K100
identified in the example HSCS.
Additional notes:
• Please see the followin
pa
es for more details on the HSSC applied instruction.
-Hi
h Speed Counter Set, HSCS FNC 53 - see pa
e 5-55
I 0 0
Counter interrupt number 6 points (1 to 6). Counter interrupts can be
entered as the output devices for Hi
h Speed Counter Set (HSCS, FNC
53). To disable the Counter Interrupts Special Auxiliar
Rela
M8059 must
be set ON.
M8000
C255
I030
K100
DHSCS