222
Useful functions
4.18.7 Batch setting Mitsubishi HMI (GOT) connection parameters (Pr. 999)
The read value is always "9999."
(1) Automatic parameter setting (Pr. 999)
Setting Pr. 999 = "10" will automatically set the communication parameters required to connect a GOT to the PU
connector.
To operate in the parameter setting mode, go to "AUTO" "GOT", then write "1".
The following tables show which parameters are changed in each of the automatic parameter settings.
GOT initial setting (PU connector) (Pr. 999 = “10”)
REMARKS
If a fault is already occurring in the drive unit, a fault cannot be initiated by Pr. 997.
The retry function is invalid for the fault initiated by the fault initiation function.
If another fault occurs after a fault has been initiated, the fault indication does not change.
The fault is not saved in the faults history either.
Communication parameters for the Mitsubishi HMI (GOT) connection can be set as a batch.
Multiple parameters are changed automatically. Users do not have to consider each parameter number. (Parameter
setting mode)
Parameter
number
Name Initial value Setting range Description
999
Automatic parameter
setting
9999
10
GOT initial setting (PU connector)
9999
No action
NOTE
y If the automatic setting is performed with Pr. 999 or the parameter setting mode, the listed settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the listed parameters will not cause any problem.
Parameter
number
Name
Initial
value
Automatically set to Refer to Page
79 Operation mode selection 0 0 147
118 PU communication speed 192 192 167
119
PU communication stop bit length 1 10 167
120
PU communication parity check 2 1 167
121
Number of PU communication retries 1 9999 167
122
PU communication check time interval 0 9999 167
123 PU communication waiting time setting 9999 0ms 167
124 PU communication CR/LF selection 1 1 167
340
Communication startup mode selection 0 1 159
549
Protocol selection 0 0 186
REMARKS
Always perform a drive unit reset after the initial setting.