101
Function assignment of external terminal and control
4
PARAMETERS
(1) Input terminal function assignment
Using Pr. 178 to Pr. 182, set the functions of the input terminals.
Refer to the following table and set the parameters:
∗1 When Pr. 59 Remote function selection ≠ "0", the functions of the RL, RM and RH signals are changed as given in the table.
∗2 The OH signal turns ON when the relay contact "opens".
(2) Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
Setting Signal Function Related Parameters
Refer to
Page
0RL
Pr. 59 = 0 (initial value) Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
80
Pr. 59 ≠ 0 ∗1 Remote setting (setting clear) Pr. 59 84
1RM
Pr. 59 = 0 (initial value) Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
80
Pr. 59 ≠ 0 ∗1 Remote setting (deceleration) Pr. 59 84
2RH
Pr. 59 = 0 (initial value) High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
80
Pr. 59 ≠ 0 ∗1 Remote setting (acceleration) Pr. 59 84
3 RT Second function selection Pr. 44, Pr. 45, Pr. 48 103
4 AU Terminal 4 input selection Pr. 267 130
5 JOG Jog operation selection Pr. 15, Pr. 16 82
7 OH External thermal relay input ∗2 Pr. 9 91
8 REX 15-speed selection (combination with three speeds RL, RM, RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
80
10 X10 Drive unit run enable signal (FR-HC, FR-CV connection) Pr. 30, Pr. 70 97
12 X12 PU operation external interlock Pr. 79 147
14 X14 PID control valid terminal Pr. 127 to Pr. 134 199
16 X16
PU/External operation switchover (turning ON X16 selects External
operation)
Pr. 79, Pr. 340 153
23 LX Pre-excitation Pr. 11, Pr. 795
94
24 MRS Output stop Pr. 17 102
25 STOP Start self-holding selection — 104
60 STF Forward rotation command (assigned to STF terminal (Pr. 178) only) — 104
61 STR Reverse rotation command (assigned to STR terminal (Pr. 179) only) — 104
62 RES Drive unit reset — —
64 X64 PID forward/reverse action switchover Pr. 127 to Pr. 134 199
65 X65
PU/NET operation switchover (turning ON X65 selects PU
operation)
Pr. 79, Pr. 340 154
66 X66
External/NET operation switchover (turning ON X66 selects NET
operation)
Pr. 79, Pr. 340 154
67 X67
Command source switchover (turning ON X67 makes Pr. 338 and Pr.
339 commands valid)
Pr. 338, Pr. 339 160
72 X72 PID integral value reset
Pr. 127 to Pr. 134, Pr. 553,
Pr. 554, Pr. 575 to Pr. 577,
C42 to C45
199
9999 — No function — —
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 182 (input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the X10 signal (FR-HC, FR-CV connection-drive unit operation enable signal) is not set or when the PU
operation external interlock (X12) signal is not assigned with Pr.79 Operation mode selection set to "7", the MRS signal
shares this function.
Same signal is used to assign multi-speed (7 speeds) and remote setting. These cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same
time.)
Turning the AU signal ON makes terminal 2 (voltage input) invalid.