York YMA024 Heat Pump User Manual


 
036-21570-002 Rev. D (0605)
Unitary Products Group 3
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-
connecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
Additional R-22 Charge / TXV Size for Various Matched Systems
Outdoor Unit YMA02411 YMA03011 YMA03611 YMA04211 YMA04811 YMA06011
Unit Orifice (s) 63 69 78 87 - 96
Approved System Thermal Expansion Valve
1,2
1TV0701 1TV0701 1TV0702 1TV0702 1TV0703 -
Factory R-22 Charge, lbs-oz 7 - 2 7 - 12 8 - 6 8 - 12 9 - 1 14 - 2
Indoor Coil
3
Coil Orifice
4
Orifice - Additional Charge, Oz
G2FD030(S,H)17 65 63/(701) + 2 69/(701) + 0 - - -
G2FD035(S,H)14 65 63/(701) + 2 69/(701) + 0 - - -
G2FD036(S,H)17 65 - - 78/(702) + 3 - - -
G2FD036(S,H)21 75 - - 78/(702) + 5 - - -
G2FD048(S,H)21,24 84 - - - 87/(702) + 3 - -
G2FD060(S,H)24 90 ----703 + 6 96 + 6
G2FD061H24 90 ----703 + 12 96 + 12
G1HA036H14 75 63/(701) + 8 69/(701) + 6 78/(702) + 5 - - -
G1HA036H17 78 63/(701) +12 69/(701) + 9 78/(702) + 8 - - -
G1HA048H21 84 - - - 87/(702) + 4 - -
G1HA060H24 90 ----703 + 6 96 + 6
G1HD036 69 63/(701) + 8 69/(701) + 5 78/(702) + 5 - - -
G1HD048 81 - - - 87/(702) + 0 - -
G1HD060 93 ----703 + 0 96 + 0
G1NA036S17J 67 63/(701) + 4 69/(701) + 2 78/(702) + 1 - - -
G1NA036S21C 67 63/(701) + 4 69/(701) + 2 78/(702) + 1 - - -
G1NA060S24T 87 - - - 87/(702) + 8 703 + 1 96 + 0
G1FA/G1UA036S14 73 63/(701) + 4 69/(701) + 2 78/(702) + 1 - - -
G1FA/G1UA036S17,21 73 63/(701) + 2 69/(701) + 0 78/(702) + 0 - - -
G1FA/G1UA048S21 84 - - - 87/(702) + 5 - -
G1FA/G1UA060S21,24 90 ----703 + 6 96 + 6
F2RC/F2FC036 75 63/(701) + 2 69/(701) + 0 ----
F2RP024 61 63/(701) + 0 -----
F2RP/F2FP030 65 63/(701) + 2 69/(701) + 0 ----
F2RP/F2FP036 75 - - 78/(702) + 5 - - -
F2FP040 63 - - 78/(702) + 8 - - -
F2RP/F2FP042 78 - - 78/(702) + 8 - - -
F2FP045 78 ----703 + 6 -
F2FP048 84 - - - 87/(702) + 7 - -
F2FP060 90 ----703 + 6 96 + 6
F2FV060 90 ----703 + 6 96 + 6
Indoor Coil with factory
installed TXV
2,4
Factory installed
coil orifice
3
Additional Charge, Oz.
G2FD030(S,H)17T - 2 0 - - -
G2FD035(S,H)14T - 2 0 - - -
G2FD036(S,H)17T - - - 3 - - -
G2FD036(S,H)21T - - - 5 - - -
G2FD060(S,H)24T - ----6 -
G1HA036H14T - - - 5 - - -
G1HA036H17T - - - 8 - - -
G1HA060H24T - ----6 -
G1FA/G1UA036S14T - - - 1 - - -
G1FA/G1UA036S17,21T - - - 0 - - -
G1FA/G1UA060S21,24T - ----6 -
F3RP024 - 0 -----
F3RP030 - 2 0 ----
F3RP036 - - - 5 - - -
F3RP042 - - - 8 - - -
F3FP040 - - - 8 - - -
F3FP060 - ----6 -
F3FV060 - ----6 -
FOOTNOTES:
1 Only the TXV kits listed above are approved for use in these systems. The charge adder is the same as that listed for the orifice.
2 Models with reciprocating compressors require start kits when matched to TXV indoor coils.
3 Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit
2FD06700224.
4 These orifices or TXVs are factory mounted in the flow device of each indoor coil (701, 702, 703 indicates 1TV07…series). A “T”
suffix indicates a coil or air handler with a factory mounted TXV.