York YMA024 Heat Pump User Manual


 
036-21570-002 Rev. D (0605)
16 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YMA06011
INDOOR COIL MODEL NO. G2FA060S24
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1600 1800 2000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57
65
T.C. 57.6 59.5 57.0 62.3 58.7 59.1 61.0 58.3 63.3 60.1 60.6 62.5 59.5 64.2 61.5
S.C. 56.2 53.7 44.2 44.1 30.5 57.7 56.6 46.8 46.4 31.9 59.3 59.5 49.4 48.8 33.3
K.W. 3.5 3.6 3.6 3.6 3.6 3.5 3.6 3.6 3.6 3.6 3.5 3.6 3.6 3.6 3.6
75
T.C. 55.1 56.6 53.8 59.1 57.7 56.6 58.2 54.9 60.2 58.8 58.2 59.9 56.0 61.3 59.9
S.C. 53.6 52.0 42.7 42.6 30.3 55.2 54.7 45.2 45.0 31.5 56.8 57.3 47.8 47.4 32.8
K.W. 4.0 4.0 4.0 4.1 4.2 4.0 4.1 4.1 4.1 4.2 4.1 4.1 4.1 4.1 4.2
85
T.C. 52.6 53.6 50.5 55.8 56.7 54.2 55.5 51.5 57.1 57.6 55.9 57.3 52.6 58.4 58.4
S.C. 51.1 50.3 41.2 41.2 30.1 52.7 52.7 43.7 43.6 31.2 54.4 55.2 46.2 46.0 32.3
K.W. 4.5 4.5 4.5 4.6 4.7 4.6 4.6 4.5 4.6 4.7 4.6 4.6 4.6 4.7 4.7
95
T.C. 50.1 50.7 47.3 52.6 55.7 51.8 52.7 48.2 54.0 56.3 53.6 54.6 49.1 55.4 56.9
S.C. 48.5 48.7 39.7 39.8 29.9 50.3 50.8 42.2 42.2 30.8 52.0 53.0 44.6 44.6 31.7
K.W. 5.0 5.0 5.0 5.1 5.2 5.1 5.1 5.0 5.1 5.2 5.1 5.1 5.1 5.2 5.3
105
T.C. 47.3 47.7 44.2 48.9 51.2 48.8 49.4 45.0 50.1 51.7 50.3 51.2 45.8 51.3 52.1
S.C. 45.8 45.8 38.3 38.3 28.3 38.9 47.7 40.4 40.7 29.4 48.7 49.5 42.6 43.0 30.4
K.W. 5.7 5.7 5.7 5.8 5.9 5.7 5.7 5.7 5.8 5.9 5.8 5.8 5.7 5.8 5.9
115
T.C. 44.5 44.8 41.1 45.4 46.8 45.8 46.3 41.9 46.3 47.1 47.1 47.8 42.7 47.2 47.5
S.C. 43.1 43.1 36.9 36.8 26.8 27.8 44.6 38.8 39.2 27.9 45.6 46.1 40.6 41.5 29.1
K.W. 6.3 6.3 6.3 6.4 6.5 6.4 6.4 6.3 6.4 6.6 6.4 6.4 6.3 6.4 6.6
125
T.C. 41.8 41.9 38.1 41.8 42.4 42.9 43.2 38.8 42.5 42.6 44.0 44.5 39.5 43.2 42.8
S.C. 40.4 40.3 35.6 35.4 25.2 16.8 41.5 37.1 37.7 26.5 42.4 42.7 38.6 40.0 27.8
K.W. 7.0 7.0 6.9 7.0 7.2 7.0 7.0 7.0 7.0 7.2 7.0 7.0 7.0 7.1 7.2
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F2FP060 0.98 0.96 1.01
F2FV060 1.00 0.97 0.98
N1VSD20 G2FD060(S,H)24(T) 0.99 0.96 0.98
N1VSD20 G2FD061H24 1.01 0.98 0.98
N1AHD20 G2FD060(S,H)24(T) 1.00 1.00 1.00
N1AHD20 G2FD061H24 1.01 1.00 1.00
G1FA060S21,24 1.00 1.00 1.00
G2FD060(S,H)24 1.00 1.00 1.00
G2FD061H24 1.01 1.00 1.00
G1NA060S24T 0.98 0.96 0.99
G1HD060 0.98 0.97 1.00
G1HA60S24 0.99 0.97 0.99
Variable Speed
Furnace
Coil
T.C. S.C. KW
P*DUC20V G1FA060S21 0.99 0.98 0.98
P*DUC20V G2FD060(S,H)24 0.99 0.98 0.98
P*DUC20V G2FD061H24 1.00 0.99 0.98
P1XUC16V G1FA060S21 0.99 0.95 0.98
P1XUC16V G2FD060(S,H)24 0.99 0.95 0.98
P1XUC16V G2FD061H24 0.99 0.95 0.98
P1XUC20V G1FA060S21 0.99 0.95 0.98
P1XUC20V G2FD060(S,H)24 0.99 0.95 0.98
P1XUC20V G2FD061H24 1.00 0.97 0.98
P1XUD20V G1FA060S24 0.99 0.95 0.98
P1XUD20V G2FD060(S,H)24 0.99 0.95 0.98
P1XUD20V G2FD061H24 1.00 0.96 0.97
P1XDC20V G2FD060(S,H)24 0.99 0.94 0.98
P1XDC20V G1HA60H24 0.98 0.93 0.96
P1XDD20V G2FD060(S,H)24 0.99 0.94 0.98
P1XDD20V G2FD061H24 1.00 0.96 0.98
P1XDD20V G1HA60H24 0.98 0.93 0.96