York YMA024 Heat Pump User Manual


 
036-21570-002 Rev. D (0605)
Unitary Products Group 11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YMA02411
INDOOR COIL MODEL NO. G2FD030S17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57
65
T.C. 22.5 25.1 25.1 28.2 30.0 25.0 26.4 26.4 29.2 30.1 27.5 27.6 27.8 30.1 30.3
S.C. 24.5 21.7 18.2 18.3 14.5 27.1 25.5 20.8 19.9 14.8 29.6 29.3 23.3 21.5 15.1
K.W. 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
75
T.C. 21.3 23.4 23.5 26.4 28.8 23.6 24.9 24.7 27.4 29.3 26.0 26.3 25.9 28.4 29.8
S.C. 23.2 20.9 17.5 17.6 14.0 25.6 24.5 20.1 19.5 14.7 28.1 28.1 22.6 21.5 15.4
K.W. 1.8 1.8 1.8 1.9 1.9 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
85
T.C. 20.1 21.7 22.0 24.7 27.7 22.3 23.3 23.0 25.7 28.5 24.5 25.0 24.1 26.8 29.3
S.C. 21.8 20.1 16.8 16.8 13.5 24.2 23.5 19.4 19.2 14.6 26.5 27.0 22.0 21.5 15.7
K.W. 1.9 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.1
95
T.C. 18.9 20.0 20.4 22.9 26.5 20.9 21.8 21.3 24.0 27.7 23.0 23.7 22.2 25.1 28.9
S.C. 20.5 19.3 16.1 16.1 13.0 22.7 22.5 18.7 18.8 14.5 24.9 25.8 21.4 21.5 16.1
K.W. 2.1 2.1 2.1 2.2 2.2 2.1 2.1 2.1 2.2 2.3 2.2 2.2 2.2 2.2 2.3
105
T.C. 17.5 18.3 18.4 20.7 24.2 19.3 20.0 19.4 21.7 25.1 21.1 21.6 20.3 22.6 26.1
S.C. 19.0 18.3 15.2 15.3 12.1 20.9 20.9 17.7 17.9 13.7 22.9 23.5 20.3 20.5 15.3
K.W. 2.2 2.2 2.2 2.3 2.4 2.3 2.3 2.2 2.3 2.4 2.4 2.3 2.3 2.4 2.4
115
T.C. 16.1 16.7 16.5 18.6 21.8 17.6 18.1 17.5 19.4 22.6 19.2 19.6 18.5 20.3 23.4
S.C. 17.4 17.3 14.3 14.5 11.2 19.1 19.3 16.7 17.0 12.8 20.9 21.2 19.2 19.5 14.4
K.W. 2.4 2.4 2.3 2.4 2.5 2.4 2.4 2.4 2.5 2.6 2.5 2.5 2.4 2.5 2.6
125
T.C. 14.7 15.0 14.5 16.5 19.5 16.0 16.3 15.6 17.2 20.1 17.4 17.6 16.7 17.9 20.7
S.C. 15.9 16.4 13.4 13.7 10.4 17.3 17.6 15.8 16.1 12.0 18.9 18.9 18.2 18.5 13.6
K.W. 2.5 2.5 2.5 2.6 2.7 2.6 2.6 2.5 2.6 2.7 2.7 2.6 2.5 2.6 2.8
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F2RC/F2FC036 1.00 1.00 1.00
F2RP/F2FP/F3FP024 0.98 0.99 0.98
F2RP/F2FP/F3FP030 1.00 1.00 1.00
N1VSB12 G2FD030(S,H)17(T) 1.01 0.98 0.92
N1AHB08 G2FD030(S,H)17(T) 1.00 1.00 1.00
N1AHB12 G2FD030(S,H)17(T) 1.00 1.00 1.00
G1FA036S14 1.01 1.02 1.00
G1FA036S17,21 1.00 1.00 1.00
G2FD030(S,H)17(T) 1.00 1.00 1.00
G2FD035(S,H)14(T) 1.00 1.00 1.00
G1NA036S17J 1.01 1.00 1.00
G1NA036S21C 1.01 1.00 1.00
G1HD036 1.02 1.03 1.00
G1HA036H14 1.03 1.00 1.00
G1HA036H17 1.03 1.01 0.99
Variable Speed
Furnace
Coil
T.C. S.C. KW
P*DUA12V G1FA036S14 1.02 0.98 0.93
P*DUA12V G2FD035(S,H)14(T) 1.01 0.98 0.92
P*DUB16V G1FA036S17 1.02 1.01 0.93
P*DUB16V G2FD030(S,H)17(T) 1.02 1.01 0.93
P*DUC20V G1FA036S21 1.02 1.01 0.93
P1XUB12V G1FA036S17 1.02 1.01 0.93
P1XUB12V G2FD030(S,H)17(T) 1.02 1.01 0.93
P1XUC16V G1FA036S21 1.01 0.99 0.92
P1XUC20V G1FA036S21 1.02 1.01 0.92
P1XDB12V G2FD030(S,H)17(T) 1.02 1.02 0.93
P1XDB12V G1HA036H17 1.03 1.01 0.93