Johnson Controls Unitary Products 23
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD36S41S1
INDOOR COIL MODEL NO. AHP36
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 37.0 40.3 39.8 43.7 47.3 39.3 41.5 41.2 45.3 48.9 41.6 42.6 42.7 46.8 50.5
S.C. 35.7 32.2 27.3 27.6 23.6 37.9 35.0 29.4 29.4 24.6 40.2 37.8 31.4 31.3 25.6
KW 2.2 2.2 2.2 2.1 2.2 2.2 2.2 2.2 2.1 2.2 2.1 2.2 2.2 2.2 2.2
75
T.C. 35.3 37.9 37.5 41.4 44.9 37.5 39.0 38.7 42.7 46.3 39.7 40.2 40.0 44.1 47.8
S.C. 34.1 31.1 26.4 26.5 22.3 36.2 33.9 28.4 28.4 23.4 38.3 36.6 30.4 30.3 24.4
KW 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
85
T.C. 33.7 35.4 35.2 39.0 42.4 35.7 36.6 36.2 40.2 43.7 37.7 37.8 37.3 41.4 45.1
S.C. 32.5 30.1 25.4 25.5 21.1 34.5 32.7 27.4 27.4 22.2 36.4 35.4 29.3 29.2 23.2
KW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
95
T.C. 32.1 33.0 32.9 36.6 39.9 33.9 34.2 33.8 37.7 41.1 35.7 35.4 34.6 38.7 42.4
S.C. 31.0 29.1 24.4 24.5 19.9 32.7 31.6 26.4 26.4 20.9 34.5 34.2 28.3 28.2 22.0
KW 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.8 2.9
105
T.C. 29.9 30.2 30.2 33.6 36.9 31.6 31.6 30.9 34.5 38.0 33.2 32.9 31.6 35.5 39.0
S.C. 28.9 27.4 23.3 23.3 18.7 30.5 29.6 25.2 25.2 19.7 32.0 31.8 27.1 27.0 20.7
KW 2.9 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.0 3.1
115
T.C. 27.8 27.6 27.5 30.7 34.0 29.3 29.1 28.1 31.5 34.9 30.8 30.5 28.7 32.3 35.8
S.C. 26.9 25.7 22.1 22.2 17.5 28.3 27.6 24.0 24.0 18.5 29.7 29.5 25.9 25.9 19.5
KW 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.3 3.3
125
T.C. 25.7 25.0 24.8 27.8 31.1 27.0 26.6 25.3 28.4 31.8 28.3 28.1 25.8 29.1 32.6
S.C. 24.8 24.1 21.0 21.0 16.4 26.1 25.6 22.9 22.9 17.4 27.3 27.2 24.7 24.7 18.4
KW 3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.3 3.4 3.5 3.4 3.4 3.4 3.5 3.6
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC37 1.00 0.99 1.00
– FC/MC/PC43 0.99 0.99 1.00
– FC/MC/PC48 1.00 1.00 1.00
– HC42 0.99 0.99 1.00
– HD48 1.00 1.00 1.00
– HD48 0.97 0.96 1.00
AV36 – 1.02 1.04 1.00
F4FP045 – 1.00 1.00 1.00
MA12B FC/MC/PC43B 0.99 0.99 1.00
MV12B FC/MC/PC43B 1.01 1.01 1.00
MV16C FC/MC/PC43C 1.01 1.01 1.00
MA14D FC/MC/PC48D 1.00 1.00 1.00
MV12D FC/MC/PC48D 1.01 1.00 1.00
MV16C FC/MC/PC48C 1.03 1.02 1.00
MV20D FC/MC/PC48D 1.03 1.02 1.00
Furnaces Coils T.C. S.C. KW
T*9X*B12 FC/MC/PC43B 1.04 1.07 0.96
T*(8,L)X*B12 FC/MC/PC43B 1.04 1.07 0.96
T*(8,L)X*C16 FC/MC/PC43C 1.04 1.05 0.92
T*9X*C16 FC/MC/PC43C 1.04 1.08 0.95
T*(8,L)X*C20 FC/MC/PC43C 1.05 1.08 0.94
T*9X*C20 FC/MC/PC43C 1.03 1.05 0.94
Y*(8,L)C*A12 FC/MC/PC37A 0.97 0.92 0.94
Y*(8,L)C*B12 FC/MC/PC43B 1.01 1.02 0.98
(Y*9C/T*9V)*B12 FC/MC/PC43B 1.01 1.02 0.98
Y*(8,L)C*C16 FC/MC/PC43C 1.02 1.03 0.95
Y*(8,L)C*C20 FC/MC/PC43C 1.02 1.03 0.94
(Y*9C/T*9V)*C16 FC/MC/PC43C 1.01 1.02 0.97
(Y*9C/T*9V)*C20 FC/MC/PC43C 1.02 1.03 0.95
Y*(8,L)C*C16 FC/MC/PC48C 1.03 1.04 0.95
Y*(8,L)C*C20 FC/MC/PC48C 1.03 1.04 0.94
(Y*9C/T*9V)*C16 FC/MC/PC48C 1.03 1.04 0.96
(Y*9C/T*9V)*C20 FC/MC/PC48C 1.03 1.07 0.98
Y*(8,L)C*C16 HC42 1.01 1.03 0.95
Y*(8,L)C*C20 HC42 1.02 1.03 0.94
(Y*9C/T*9V)*C16 HC42 1.01 1.02 0.97
(Y*9C/T*9V)*C20 HC42 1.01 1.03 0.95
Y*(8,L)C*B12 HD48 1.00 1.01 0.97
Y*(8,L)C*C16 HD48 1.02 1.03 0.94
Y*(8,L)C*C20 HD48 1.03 1.03 0.94
(Y*9C/T*9V)*B12 HD48 1.00 1.01 0.97
(Y*9C/T*9V)*C16 HD48 1.02 1.02 0.95
(Y*9C/T*9V)*C20 HD48 1.02 1.06 0.98
Y*(8,L)C*C16 UC48C 1.02 1.04 0.95
Y*(8,L)C*C20 UC48C 1.03 1.05 0.94
(Y*9C/T*9V)*C16 UC48C 1.02 1.04 0.96
(Y*9C/T*9V)*C20 UC48C 1.03 1.08 0.98
Furnaces Coils T.C. S.C. KW