York WR 180 Air Conditioner User Manual


 
262292-YTG-B-0107
50 Unitary Products Group
FIGURE 17:FOUR AND SIX POINT LOADS
A
D
C
E
B
F
A
D
B
C
TABLE 36: FOUR AND SIX POINT LOADS
Unit Size
Operating
Weight
4 Point Loads (lbs)
ABC D
WR180 Gas 2900 495 924 965 516
WR240 Gas 3200 558 1042 1042 558
WR300 Gas 3300 575 1075 1075 575
WR180 Elec 2700 460 860 898 481
WR240 Elec 3000 523 977 977 523
WR300 Elec 3100 540 1010 1010 540
Unit Size
Operating
Weight
6 Point Loads (lbs)
ABC D E F
WR180 Gas 2900 330 344 494 643 616 473
WR240 Gas 3200 372 372 533 695 695 533
WR300 Gas 3300 383 383 550 717 717 550
WR180 Elec 2700 307 321 460 599 573 440
WR240 Elec 3000 349 349 500 651 651 500
WR300 Elec 3100 360 360 517 673 673 517