NOTE 1: HACR Type per NEC.
TABLE 28: WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET
MODEL
(TONNAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
240
(20)
208 30.1 225 2.4 20.0 0.0
None 0.0 - - 97.3 125
E18 13.5 1 37.5 97.3 125
E36 27.0 2 75.1 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
230 30.1 225 2.4 20.0 0.0
None 0.0 - - 97.3 125
E18 18.0 1 43.3 97.3 125
E36 36.0 2 86.6 133.3 150
E54 54.0 2 129.9 154.9 175
E72 72.0 2 173.2 198.2 225
460 15.5 114 0.9 10.0 0.0
None 0.0 - - 48.5 60
E18 18.0 1 21.7 48.5 60
E36 36.0 2 43.3 66.6 70
E54 54.0 2 65.0 77.5 90
E72 72.0 2 86.6 99.1 110
575 12.1 80 0.6 7.5 0.0
None 0.0 - - 37.1 45
E18 18.0 1 17.3 37.1 45
E36 36.0 2 34.6 52.7 60
E54 54.0 2 52.0 61.3 70
E72 72.0 2 69.3 78.7 90
300
(25)
208 42.3 245 2.4 20.0 0.0
None 0.0 - - 124.8 150
E18 13.5 1 37.5 124.8 150
E36 27.0 2 75.1 124.8 150
E54 40.6 2 112.6 165.9 175
E72 54.1 2 150.1 175.2 200
230 42.3 245 2.4 20.0 0.0
None 0.0 - - 124.8 150
E18 18.0 1 43.3 124.8 150
E36 36.0 2 86.6 133.3 150
E54 54.0 2 129.9 154.9 175
E72 72.0 2 173.2 198.2 225
460 17.6 125 0.9 10.0 0.0
None 0.0 - - 53.2 70
E18 18.0 1 21.7 53.2 70
E36 36.0 2 43.3 66.6 70
E54 54.0 2 65.0 77.5 90
E72 72.0 2 86.6 99.1 110
575 14.5 100 0.6 7.5 0.0
None 0.0 - - 42.5 50
E18 18.0 1 17.3 42.5 50
E36 36.0 2 34.6 52.7 60
E54 54.0 2 52.0 61.3 70
E72 72.0 2 69.3 78.7 90
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
575-3-60 518 630 600 575 0.92
1. Utilization Range “A” in accordance with ARI Standard 110.