York WR 180 Air Conditioner User Manual


 
262292-YTG-B-0107
40 Unitary Products Group
NOTE 1: HACR Type per NEC.
TABLE 27: WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET
MODEL
(TONNAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
180
(15)
208 22.4 164 2.1 20.0 0.0
None - - - 78.8 100
E18 13.5 1 37.5 78.8 100
E36 27 2 74.9 118.7 125
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 175.2 200
230 22.4 164 2.1 20.0 0.0
None - - - 78.8 100
E18 18.0 1 43.3 79.1 100
E36 36.0 2 86.6 133.3 150
E54 54.0 2 129.9 154.9 175
E72 72.0 2 173.2 198.2 225
460 10.9 100 1.2 10.0 0.0
None - - - 39.3 50
E18 18.0 1 21.7 39.6 50
E36 36.0 2 43.3 66.6 70
E54 54.0 2 65.0 77.5 90
E72 72.0 2 86.6 99.1 110
575 8.3 78 0.9 7.5 0.0
None - - - 29.8 35
E18 18.0 1 17.3 31.0 35
E36 36.0 2 34.6 52.7 60
E54 54.0 2 52.0 61.3 70
E72 72.0 2 69.3 78.7 90
240
(20)
208 30.1 225 2.4 38.6 0.0
None - - - 118.1 150
E18 13.5 1 37.5 118.1 150
E36 27 2 74.9 141.9 150
E54 40.6 2 112.7 189.1 200
E72 54.1 2 150.2 198.4 225
230 30.1 225 2.4 38.6 0.0
None - - - 118.1 150
E18 18.0 1 43.3 118.1 150
E36 36.0 2 86.6 156.5 175
E54 54.0 2 129.9 178.2 200
E72 72.0 2 173.2 221.5 250
460 15.5 114 0.9 19.3 0.0
None - - - 58.7 70
E18 18.0 1 21.7 58.7 70
E36 36.0 2 43.3 78.3 80
E54 54.0 2 65.0 89.1 100
E72 72.0 2 86.6 110.7 125
575 12.1 80 0.6 16.2 0.0
None - - - 46.9 60
E18 18.0 1 17.3 46.9 60
E36 36.0 2 34.6 63.6 70
E54 54.0 2 52.0 72.2 80
E72 72.0 2 69.3 89.5 100
300
(25)
208 42.3 245 2.4 38.6 0.0
None - - - 143.4 175
E18 13.5 1 37.5 143.4 175
E36 27 2 74.9 143.4 175
E54 40.6 2 112.7 189.1 200
E72 54.1 2 150.2 198.4 225
230 42.3 245 2.4 38.6 0.0
None - - - 143.4 175
E18 18.0 1 43.3 143.4 175
E36 36.0 2 86.6 156.5 175
E54 54.0 2 129.9 178.2 200
E72 72.0 2 173.2 221.5 250
460 17.6 125 0.9 19.3 0.0
None - - - 62.9 80
E18 18.0 1 21.7 62.9 80
E36 36.0 2 43.3 78.3 80
E54 54.0 2 65.0 89.1 100
E72 72.0 2 86.6 110.7 125
575 14.5 100 0.6 16.2 0.0
None - - - 51.7 60
E18 18.0 1 17.3 51.7 60
E36 36.0 2 34.6 63.6 70
E54 54.0 2 52.0 72.2 80
E72 72.0 2 69.3 89.5 100
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
575-3-60 518 630 600 575 0.92
1. Utilization Range “A” in accordance with ARI Standard 110.