York WR 180 Air Conditioner User Manual


 
262292-YTG-B-0107
Unitary Products Group 19
TABLE 8: COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE)
Air on Evaporator Coil
Temperature of Air on Condenser Coil
75°F 85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
6000
67 100 15.9 20 18 16 14 12 10 94 16.6 13 12 11 9 8 7
62 93 15.1 444240383635 86 15.9 302927262523
57 83 15.1 504846454341 77 15.8 343332302928
7000
67 109 15.8 31 28 24 21 18 15 103 16.5 25 23 20 18 15 12
62 102 15.1 686562595653 95 15.8 575452494744
57 90 15.0 747471686461 85 15.7 636360585552
8000
67 119 15.7 42 37 33 29 24 20 112 16.4 38 34 30 26 22 18
62 110 15.0 92 88 83 79 75 70 103 15.8 84 80 76 72 69 65
57 98 14.9
98 98 95 91 86 82 93 15.7 93 93 89 85 81 77
8450
67 113 15.7 42 38 33 29 25 21 107 16.4 39 35 31 27 23 19
62 105 15.0 888885807672 98 15.8 848480767268
57 93 14.9
93 93 92 87 83 79 88 15.7 88 88 86 82 78 75
8900
67 107 15.7 42 38 34 30 26 22 101 16.4 40 36 32 29 25 21
62 99 14.9 888886827873 93 15.8 848483797571
57 88 14.9
88 88 88 84 80 76 84 15.7 84 84 84 80 76 72
95°F 105°F
6000
67 87 17.3 7 6 5 5 4 3 77 18.2 3 3 3 2 2 2
62 79 16.7 16 15 14 14 13 12 68 17.7 8 7 7 7 6 6
57 72 16.5 18 18 17 16 16 15 63 17.4 9 9 9 8 8 7
7000
67 96 17.2 20 18 16 14 12 10 86 18.2 15 14 12 11 9 7
62 88 16.6 464442403835 76 17.7 363533323028
57 79 16.4 535250484644 70 17.4 434341403836
8000
67 106 17.2 343027232016 94 18.2 282522191613
62 96 16.6 767369666259 84 17.7 656259575451
57 87 16.4
87 86 83 79 76 72 78 17.4 78 77 74 71 68 65
8450
67 101 17.2 363229252218 90 18.1 292623201714
62 92 16.6 787875716864 80 17.6 686663605754
57 83 16.4
83 83 81 77 74 70 74 17.3 74 74 72 69 67 64
8900
67 96 17.2 383531272420 86 18.1 302724211916
62 87 16.6 797979757267 76 17.6 716966636057
57 79 16.4
79 79 79 75 72 68 71 17.3 71 71 71 68 65 62
115°F 125°F
6000
67 67 19.1 - - - - - - 57 20.0 - - - - - -
62 57 18.7 - - - - - - 46 19.7 - - - - - -
57 54 18.3 - - - - - - 46 19.2 - - - - - -
7000
67 75 19.1 11 10 8 7 6 5 64 20.1 6 5 5 4 3 3
62 64 18.7 272625242321 52 19.7 181716161514
57 61 18.3 343332313029 52 19.2 252424232222
8000
67 83 19.2 21 19 17 15 13 10 72 20.1 15 14 12 11 9 7
62 71 18.7 545250474543 58 19.8 434140383735
57 68 18.3
68 67 65 62 60 58 58 19.3 58 57 56 54 52 51
8450
67 80 19.1 22 19 17 15 13 11 70 20.0 14 13 12 10 9 7
62 68 18.6 555351484644 56 19.7 414038373634
57 65 18.2
65 65 64 61 59 57 56 19.2 56 56 55 54 52 51
8900
67 77 19.0 22 20 18 16 14 12 67 19.9 13 12 11 10 9 7
62 65 18.5 555351494745 54 19.5 403837363533
57 63 18.2
63 63 63 61 59 56 54 19.0 54 54 54 53 52 51
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity