York TCGF60 Air Conditioner User Manual


 
413432-YTG-A-0608
Johnson Controls Unitary Products 3
Additional R-410A Charge / Orifice Size for Various Matched Systems
Outdoor Unit TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCGF42S41S1 TCGF48S41S1 TCGF60S41S1
Required Orifice or TXV
1
1TVM902 1TVM903 1TVM903 1TVM903 1TVM905 1TVM906
Factory Charge, lbs-oz 3 - 2 3 - 7 3 - 10 4 - 4 4 - 9 5 - 9
Indoor Coil
2,3,4
Additional Charge, Oz
FC/MC/PC24A3X 5
FC/MC/PC24B3X 5
FC/MC/PC30A3X 12 2
FC/MC/PC30B3X 12 2
FC/MC/PC32A3X 16 10
FC/MC/PC35B3X 16 10 8
FC/MC/PC35C3X 16 10 8
FC/MC/PC36A3X 8 4 1
FC/MC/PC36B3X 8 4 1
FC/MC/PC36C3X 8 4 1
FC/MC/PC37A3X 24 19 15
FC/MC/PC43B3X 24 19 15 5
FC/MC/PC43C3X 24 19 15 5
FC/MC/PC48C3X 40 32 15 17 16
FC/MC/PC48D3X 40 32 27 17 16
FC/MC/PC60D3X 17 16 0
FC/MC62D3X 25 26 18
UC24A3X 8
UC24B3X 8
UC30A3X 8 4
UC30B3X 8 4
UC36A3X
UC36B3X
UC36C3X
UC42B3X
UC42C3X
UC48C3X
UC48D3X
UC60C3X 12
UC60D3X 12
HC18A3X
HC30A3X 10
HC36B3X 16 11 8
HC42C3X 25 19 15 6
HC60D3X 0 0 0
HD24*3X 16
HD36*3X 18
HD48*3X 51 42 36 24 25
HD60*3X 24
AHP18B3X
AHP24B3X 3
AHP30B3X 16
AHP36C3X 19 15
AHP42C3X
AHP/SHP60D3X 1
AV24B3X 3
AV36C3X 25 19 15
AV/SV48D3X 9 0 1
AV/SV60D3X 0 1 0
For notes see Page 4.