York TCGF60 Air Conditioner User Manual


 
413432-YTG-A-0608
20 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGF48S41S1
INDOOR COIL MODEL NO. FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 44.1 45.2 43.0 47.2 47.3 44.2 45.3 43.9 47.4 47.9 44.2 45.3 44.8 47.6 48.5
S.C. 43.7 39.0 33.0 31.2 24.2 44.3 40.6 34.5 32.2 24.8 44.9 42.3 36.0 33.2 25.5
KW 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
75
T.C. 42.6 43.5 41.7 45.7 46.9 43.0 43.8 42.5 46.1 47.5 43.5 44.1 43.2 46.5 48.2
S.C. 42.4 39.0 33.0 31.3 24.3 43.3 40.8 34.6 32.6 25.0 44.1 42.6 36.3 33.9 25.7
KW 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6
85
T.C. 41.0 41.9 40.4 44.1 46.5 41.9 42.4 41.0 44.8 47.2 42.7 42.9 41.6 45.4 47.9
S.C. 41.1 38.9 32.9 31.4 24.3 42.2 40.9 34.7 33.0 25.2 43.4 42.9 36.6 34.6 26.0
KW 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9
95
T.C. 39.5 40.2 39.1 42.6 46.0 40.7 41.0 39.5 43.5 46.8 42.0 41.8 40.0 44.3 47.6
S.C. 39.8 38.9 32.8 31.5 24.4 41.2 41.1 34.8 33.4 25.3 42.6 43.2 36.9 35.2 26.3
KW 3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2
105
T.C. 37.1 37.6 36.0 39.8 43.4 38.3 38.6 36.6 40.6 44.1 39.5 39.6 37.2 41.4 44.8
S.C. 37.3 36.8 31.4 30.5 23.5 38.6 38.7 33.5 32.5 24.6 40.0 40.5 35.5 34.4 25.7
KW 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7
115
T.C. 34.9 35.0 33.0 37.1 40.8 36.0 36.3 33.7 37.8 41.5 37.1 37.5 34.4 38.5 42.1
S.C. 34.8 34.8 30.0 29.5 22.7 36.2 36.4 32.1 31.6 24.0 37.5 37.9 34.2 33.6 25.2
KW 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1
125
T.C. 32.6 32.5 30.1 34.4 38.2 33.6 33.9 30.8 35.0 38.8 34.6 35.4 31.6 35.7 39.5
S.C. 32.4 32.9 28.7 28.4 21.9 33.7 34.1 30.8 30.6 23.3 34.9 35.3 32.9 32.9 24.6
KW 4.4 4.4 4.4 4.5 4.6 4.4 4.4 4.4 4.5 4.6 4.5 4.5 4.4 4.5 4.6
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
- FC/MC/PC48 1.00 1.00 1.00
- FC/MC62 1.01 1.00 1.00
- HD48 1.00 1.00 1.00
- HD60 1.02 1.02 1.00
AHP/SHP60 - 0.95 0.94 0.97
AV/SV48 - 0.95 0.94 0.96
AV/SV60 - 0.95 0.94 0.96
F4FV060 - 0.95 0.94 0.96
F5FP048 - 1.01 1.04 0.97
F5FP060 - 0.95 0.95 0.98
MA16C FC/MC48C 1.00 1.00 1.00
MA20D FC/MC48D 1.00 1.00 1.00
MV16C FC/MC48C 1.01 1.01 0.96
MV20D FC/MC48D 1.01 1.01 0.96
MA16C FC/MC60C 1.00 1.00 1.00
MA20D FC/MC60D 1.00 1.00 1.00
MV20D FC/MC60D 1.01 1.01 0.96
MA20D FC/MC62D 1.01 1.00 1.00
MV20D FC/MC62D 1.02 1.01 0.96
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*C16 FC/MC/PC48C 0.99 0.97 0.98
PV8*C20 FC/MC/PC48C 1.00 1.00 0.99
P(C,V)9*C16 FC/MC/PC48C 1.00 1.00 1.00
P(C,V)9*C20 FC/MC/PC48C 1.00 1.01 0.98
PV8*C16 FC/MC/PC60C 0.99 0.98 0.98
PV8*C20 FC/MC/PC60C 1.01 1.01 0.98
P(C,V)9*C16 FC/MC/PC60C 1.00 1.00 1.00
P(C,V)9*C20 FC/MC/PC60C 1.00 1.00 0.98
P(C,V)9*D20 FC/MC/PC60D 1.01 1.01 0.97
PV8*C16 HD48 0.99 0.97 0.98
PV8*C20 HD48 1.00 1.00 0.98
P(C,V)9*C16 HD48 1.00 1.00 1.00
P(C,V)9*C20 HD48 1.00 1.00 0.98
P(C,V)9*D20 HD48 1.01 1.00 0.97
PV8*C16 HD60 1.01 0.99 0.98
PV8*C20 HD60 1.02 1.02 0.98
P(C,V)9*C16 HD60 1.02 1.02 1.00
P(C,V)9*C20 HD60 1.02 1.02 0.98
P(C,V)9*D20 HD60 1.02 1.03 0.97
PV8*C20 FC/MC62D 1.01 1.01 0.98
P(C,V)9*C16 FC/MC62D 1.01 1.00 1.00
P(C,V)9*C20 FC/MC62D 1.01 1.01 0.98
P(C,V)9*D20 FC/MC62D 1.01 1.01 0.97