York TCGF60 Air Conditioner User Manual


 
413432-YTG-A-0608
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
MODEL TCGF24S41S1 TCGF30S41S1 TCGF36S41S1 TCGF42S41S1 TCGF48S41S1 TCGF60S41S1
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 16.8 18.4 19.09 23.9 27.9 35.9
Max. Overcurrent Device Amps
2
25 30 30 40 45 60
Min. Overcurrent Device Amps
3
20 20 20 25 30 40
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll
Compressor
Amps
Rated Load 12.8 14.1 14.1 17.9 21.1 27.5
Locked Rotor 58 73 77 112 115 135
Crankcase Heater No No No No No No
Fan Motor Amps Rated Load .8 .8 1.5 1.5 1.5 1.5
Fan Diameter Inches 22 22 22 24 24 24
Fan Motor
Rated HP 1/8 1/8 1/4 1/4 1/4 1/4
Nominal RPM 1075 1075 850 850 850 850
Nominal CFM 2750 2800 3200 3600 3600 3700
Coil
Face Area Sq. Ft. 13.07 17.44 17.44 20.03 21.37 24.04
Rows Deep 1 1 1 1 1 1
Fin / Inches 23 23 23 23 23 23
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 7/8 7/8 1 1/8
Unit Charge (Lbs. - Oz.)
4
3 - 2 3 - 3 - 10 4 - 4 4 - 9 5 - 9
Charge Per Foot, Oz. 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. TBD 130 145 172 180 199
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B C Liquid Vapor
24 28 29 29
3/8”
3/4”30 36 29 29
36 36 29 29
42 34 33.6 33.6
7/8”
48 36 33.6 33.6
60 40 33.6 33.6
7/8”
2
2. Adapter fitting required for 1-1/8” line set.