York R-410A Air Conditioner User Manual


 
528194-YTG-F-1210
Johnson Controls Unitary Products 39
120
(10)
208 13.9 110 21.7 3.5 9.6 5.5 0
None - - - 47.9 53.4 60 60
E18 13.5 2 37.5 58.8 65.7 60 70
E24 18 2 50.0 74.5 81.3 80 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.7 175 175
230 13.9 110 21.7 3.5 9.6 5.5 0
None - - - 47.9 53.4 60 60
E18 18 2 43.3 66.1 73 70 80
E24 24 2 57.7 84.2 91 90 100
E36 34 2 81.8 114.2 121.1 125 125
E54 54 2 129.9 141.9 148.8 175 175
460 7.4 55 11.5 1.6 4.8 2.2 0
None - - - 24.7 26.9 30 30
E18 18 2 21.7 33.1 35.8 35 40
E24 24 2 28.9 42.1 44.8 45 45
E36 34 2 40.9 57.1 59.9 60 60
E54 54 2 65.0 71 73.7 80 80
575 5.6 43 8.7 1.3 3.9 1.8 0
None - - - 19.1 20.9 20 25
E18 18 2 17.3 26.5 28.8 30 30
E24 24 2 23.1 33.7 36 35 40
E36 34 2 32.7 45.8 48 50 50
E54 54 2 52.0 56.8 59.1 70 70
150
(12.5)
208 23.1 160 36 3.5 15.2 5.5 0
None - - - 81.2 86.7 100 100
E18 13.5 2 37.5 81.2 86.7 100 100
E24 18 2 50.0 81.5 88.3 100 100
E36 25.5 2 70.8 107.5 114.4 110 125
E54 40.6 2 112.7 159.9 166.7 175 175
230 23.1 160 36 3.5 15.2 5.5 0
None - - - 81.2 86.7 100 100
E18 18 2 43.3 81.2 86.7 100 100
E24 24 2 57.7 91.2 98.0 100 100
E36 34 2 81.8 121.2 128.1 125 150
E54 54 2 129.9 148.9 155.8 175 175
460 12.2 87 19 1.6 7.6 2.2 0
None - - - 41.5 43.7 50 50
E18 18 2 21.7 41.5 43.7 50 50
E24 24 2 28.9 45.6 48.3 50 50
E36 34 2 40.9 60.6 63.4 70 70
E54 54 2 65.0 74.5 77.2 90 90
575 8.7 62 13.5 1.3 6.1 1.8 0
None - - - 30.9 32.7 35 40
E18 18 2 17.3 30.9 32.7 35 40
E24 24 2 23.1 36.5 38.7 40 40
E36 34 2 32.7 48.5 50.8 50 60
E54 54 2 52.0 59.6 61.8 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps