York R-410A Air Conditioner User Manual


 
528194-YTG-F-1210
Johnson Controls Unitary Products 37
120
(10)
208 13.9 110 21.7 3.5 6.8 5.5 0
None---45.150.650 60
E18 13.5 2 37.5 55.3 62.2 60 70
E24 18 2 50.0 71 77.8 80 80
E36 25.5 2 70.8 97 103.9 100 110
E54 40.6 2 112.7 149.4 156.2 150 175
230 13.9 110 21.7 3.5 6.8 5.5 0
None---45.150.650 60
E18 18 2 43.3 62.6 69.5 70 70
E24 24 2 57.7 80.7 87.5 90 90
E36 34 2 81.8 110.7 117.6 125 125
E54 54 2 129.9 138.4 145.3 150 175
460 7.4 55 11.5 1.6 3.4 2.2 0
None---23.325.530 30
E18 18 2 21.7 31.3 34.1 35 35
E24 24 2 28.9 40.3 43.1 45 45
E36 34 2 40.9 55.4 58.1 60 60
E54 54 2 65.0 69.2 72 80 80
575 5.6 43 8.7 1.3 2.7 1.8 0
None---17.919.720 25
E18 18 2 17.3 25 27.3 25 30
E24 24 2 23.1 32.2 34.5 35 35
E36 34 2 32.7 44.3 46.5 45 50
E54 54 2 52.0 55.3 57.6 60 60
150
(12.5)
208 23.1 160 36 3.5 9.6 5.5 0
None - - - 75.6 81.1 90 100
E18 13.5 2 37.5 75.6 81.1 90 100
E24 18 2 50.0 75.6 81.3 90 100
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.7 175 175
230 23.1 160 36 3.5 9.6 5.5 0
None - - - 75.6 81.1 90 100
E18 18 2 43.3 75.6 81.1 90 100
E24 24 2 57.7 84.2 91.0 90 100
E36 34 2 81.8 114.2 121.1 125 125
E54 54 2 129.9 141.9 148.8 175 175
460 12.2 87 19 1.6 4.8 2.2 0
None---38.740.950 50
E18 18 2 21.7 38.7 40.9 50 50
E24 24 2 28.9 42.1 44.8 50 50
E36 34 2 40.9 57.1 59.9 60 60
E54 54 2 65.0 71.0 73.7 80 80
575 8.7 62 13.5 1.3 3.9 1.8 0
None---28.730.535 35
E18 18 2 17.3 28.7 30.5 35 35
E24 24 2 23.1 33.7 36.0 35 40
E36 34 2 32.7 45.8 48.0 50 50
E54 54 2 52.0 56.8 59.1 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZF078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps