York K5EU090A50A Fan User Manual


 
8 Unitary Products Group
550.39-N4YI
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
1
- (CFM)
BLOWER
SPEED
RPM
AIRFLOW
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(KW)
ESP2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW
2400 CFM 2700 CFM 3000 CFM 3300 CFM 3600CFM
600 0.35 0.62 0.59 0.26 0.70 0.66 0.13 0.78 0.73 ------
655 0.49 0.70 0.66 0.41 0.78 0.72 0.30 0.87 0.82 0.07 0.96 0.90 - - -
700 0.60 0.77 0.73 053 0.85 0.80 043 0.95 0.89 0.29 1.06 0.99 0.12 1.17 1.09
800 0.92 0.97 0.90 0.85 1.06 0.99 0.77 1.18 1.10 0.65 1.30 1.21 0.49 1.42 1.32
880 1.18 1.11 1.04 1.11 1.24 1.16 1.03 1.37 1.28 0.91 1.50 1.38 0.77 1.64 1.53
900 1.24 1.15 1.07 1.18 1.28 1.19 1.10 1.42 1.32 0.98 1.55 1.43 0.84- 1.70 1.57
1000 1.58 1.35 1.26 1.53 1.48 1.38 1.46 1.63 1.48 1.37 1.81 1.65 1.24 2.02 1.85
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
1
-(m
3
/s)
BLOWER
SPEED
RPM
AIRFLOW
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
1.1 m
3
/s 1.3 m
3
/s 1.4 m
3
/s 1.6 m
3
/s 1.7 m
3
/s
600 87 0.46 0.59 64 0.52 0.66 32 0.45 0.73 ------
655 122 0.52 0.66 102 0.58 0.72 74 0.65 0.82 17 0.72 0.90 - - -
700 149 0.57 0.73 131 0.63 0.80 107 0.71 0.89 72 0.79 0.99 30 0.87 1.09
800 228 0.72 0.90 211 0.79 0.99 191 0.88 1.10 161 0.97 1.21 122 1.06 1.32
880 293 0.83 1.04 275 0.92 1.16 255 1.02 1.28 226 1.12 1.38 191 1.22 1.53
900 308 0.86 1.07 293 0.95 1.19 273 1.06 1.32 243 1.15 1.43 208 1.27 1.57
1000 392 1.01 1.26 379 1.10 1.38 362 1.21 1.48 340 1.35 1.65 308 1.50 1.85
KEU120- SUPPLY AIR BLOWER PERFORMANCE
1
(CFM)
BLOWE
R
SPEED
RPM
AIRFLOW
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
3200 3600 4000 4400 4800
700 0.49 1.01 0.94 0.34 1.17 1.09 0.14 1.33 1.24 ------
800 0.84 1.25 1.16 0.71 1.42 1.32 0.53 1.60 1.48 0.30 1.80 1.64 - - -
900 1.18 1.48 1.38 1.06 1.70 1.57 0.91 1.92 1.75 0.70 2.18 1.99 0.43 2.45 2.24
950 1.37 1.61 1.50 1.26 1.86 1.71 1.11 2.12 1.95 0.90 2.39 2.18 0.65 2.67 2.44
1000 1.56 1.75 1.62 1.46 2.02 1.85 1.32 2.30 2.10 1.13 2.60 2.38 0.87 2.90 2.65
KEU120 - SUPPPLY AIR BLOWER PERFORMANCE
1
(m
3
/s)
BLOWE
R
SPEED
RPM
AIRFLOW
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
1.5 m
3
/s 1.7m
3
/s 1.9 m
3
/s 2.0 m
3
/s 2.3 m
3
/s
700 122 0.75 0.94 84 0.87 1.09 35 0.99 1.24 ------
800 208 0.93 1.16 176 1.05 1.32 131 1.19 1.48 74 1034 1.64 - - -
900 293 1.10 1.38 263 1.27 1.57 226 1.43 1.75 174 1.62 1.99 107 1.83 2.24
950 340 1.20 1.50 312 1.39 1.71 275 1.58 1.95 223 1.78 2.18 161 1.99 2.44
1000 387 1.30 1.62 362 1.50 1.85 327 1.71 2.10 280 1.94 2.38 216 2.16 2.65
1
Unit resistance is based on a wet evaporator coil and clean filters.
2
Availablestaticpressure inIWG(Pa) to overcome the resistanceof the duct systemand anyaccessoriesadded to the unit. Refer toTable 6 for the resistanceof these
accessories andto Table 7 for additionalmotor and drivedata
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
LEGEND:
TABLE 4 - BLOWER PERFORMANCE
RPM range for the standard factory-mounted drive com
-
ponents.
Exceeds the BHP limitation of the standard
factory-mounted blower motor