TABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY
UNIT MODEL HEATER MODEL VOLTAGE TEST
NOMINAL RATINGS
1
CAPACITY
1ST STAGE 2ND STAGE
KW MBH KW MBH KW MBH
060
2HT045010 25 208 / 240
2
10 34.2 10 34.2 - -
2HT045016 25 208 / 240
2
16 54.7 10 34.2 6 20.5
2HT045026 25 208 / 240
2
26 88.9 16 54.7 10 34.2
090, 120
2HS045010
25 208 / 240
2
10 34.2 10 34.2 - -46 480
3
58 600
4
2HS045016
25 208 / 240
2
16 54.7 10 34.2 6 20.546 480
3
58 600
4
2HS045026
25 208 / 240
2
26 88.9 16 54.7 10 34.246 480
3
58 600
4
2HS045036
25 208 / 240
2
36 123 16 54.7 20 68.346 480
3
58 600
4
180
2HS045010
25 208 / 240
2
10 34.2 10 34.2 - -46 280
3
58 600
4
2HS045016
25 208 / 240
2
16 54.7 10 34.2 6 20.546 280
3
58 600
4
2HS045026
25 208 / 240
2
26 88.9 16 54.7 10 34.246 280
3
58 600
4
2HS045036
25 208 / 240
2
36 123 16 54.7 20 68.346 280
3
58 600
4
2HS045072
25 208 / 240
2
72 246 36 123 36 12346 280
3
58 600
4
1. Capacity Ratings do not include the heat generated by the air blower motor.
2. For 208 volts, multiply the MBH and KW by (208/240)² or 0.751.
For 230 volts, multiply the MBH and KW by (230/240)² or 0.918.
3. For 460 volts, multiply the MBH and KW by (460/480)² or 0.918.