York K3EU180 Air Conditioner User Manual


 
036-21300-002-A-0905
6 Unitary Products Group
NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are
for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each sys-
tem. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level rat-
ings.
FIGURE 4 - SUSPENSION ACCESSORY (HORIZONTAL) - KEU180
6XVSHQVLRQ
&KDQQHOV

+DQJHU5RGV
)LHOG6XSSOLHG
&2,/
6(&7,21
%/2:(5
6(&7,21
5(7851$,5*5,//(
$FFHVVRU\,QVWDOOHG
2Q7KLV(QG2I8QLW
6833/<$,53/(180
$QG(/(&75,&+($7(5
$FFHVVRULHV,QVWDOOHG2Q
7KLV(QG2I8QLW
$,5287
$,5,1
5HIHUWR3DUW1R
IRU
LQVWDOODWLRQLQVWUXFWLRQVRQ
WKHVXVSHQVLRQDFFHVVRU\
DQGIRUWKHLQGLYLGXDOORDG
RQHDFKKDQJHUURG
TABLE 3: SOUND POWER RATINGS
UNIT
MODEL
CFM
ESP BLOWER
SOUND POWER (dB 10
-12
WATTS)
OCTAVE BAND CENTERLINE FREQUENCY (HZ)
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 SWL dB(a)
dB(A)
@
10 FT.
1
060 2,000 0.50 940 0.70 88 88 78 71 73 66 61 56 77 44
090 3,000 0.60 750 1.05 88 88 78 73 71 66 61 56 77 45
120 4,000 0.70 850 1.75 91 91 81 74 76 69 64 59 81 48
180 6,000 0.75 750 2.75 95 95 85 80 78 73 68 63 84 52
1. At a distance of 10 feet from the blower.