York DH 180 Air Conditioner User Manual


 
262260-YTG-E-1008
Johnson Controls Unitary Products 41
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility.
York's Sunline Ultra™ units are convertible single package
units. All models have dual independent refrigerant circuits
for efficient part load operation and maximum comfort con-
trol. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at
ground level or set on steel beams above a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factory-
mounted options and field-installed accessories to make
them suitable for almost every application. All units are self-
contained and assembled on full perimeter base rails with
holes in the four corners for overhead rigging. Every unit is
completely piped, wired, charged and tested at the factory
to simplify the field installation and to provide years of
dependable operation. All models (including those with an
economizer) are suitable for either bottom or horizontal duct
connections. Models with power exhaust are suitable for
bottom duct connections only. For bottom duct, remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, replace the
supply and return air panels on the rear of the unit with a
side duct flange accessory. All supply air blowers are
equipped with a belt drive that can be adjusted to meet the
exact requirements of the job. A high static drive option is
available for applications with a higher CFM and/or static
pressure requirement.
Each unit shall have 2 condenser fan motors. All compres-
sors include crankcase heat and internal pressure relief.
Every refrigerant circuit includes an expansion valve, a liq-
uid line filter-drier, a discharge line high pressure switch and
a suction line with a freezestat and low pressure/loss of
charge switch. The unit control circuit includes a 75 VA
transformer, a 24-volt circuit breaker and a relay board with
two compressor lockout circuits, a terminal strip for thermo-
stat wiring, plus an additional set of pin connectors to sim-
plify the interface of additional field controls. All models are
CSA approved. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry an additional 4-year warranty. Aluminized steel
tubular heat exchangers carry an additional 9-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, DH***N
Electric Cooling/Gas Heat, DH***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted instal-
lation. The 15 ton units shall have minimum EER ratings of
10.8, the 17.5 ton units shall have minimum EER ratings of
10.2, the 20 ton units shall have minimum EER ratings of 9.7
and the 25 ton units shall have minimum EER ratings of 9.6.
They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge
supply/return, and be available with factory installed options
or field installed accessories. The units shall be factory
wired, piped, charged with R-22 refrigerant and factory
tested prior to shipment. All unit wiring shall be both num-
bered and color coded. All units shall be manufactured in a
facility certified to ISO 9001 standards and the cooling per-
formance shall be rated in accordance with DOE and ARI
test procedures. Units shall be CSA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90
conditions.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel, with
exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hour salt spray test per ASTM-
B117 standards. Indoor blower section shall be insulated
with a minimum 1/2" thick insulation, coated on the airside.
Aluminum foil faced insulation shall be used in the furnace
compartment and be fastened with ridged fasteners to pre-
vent insulation from entering the air stream. Cabinet panels
shall be "large" size, easily removable for servicing and
maintenance. Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 2" fil-
ters shall be furnished and be accessible through a remov-
able access door, sealed airtight. Units filter track shall be
designed to accommodate either 2" or 4" filters. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evapora-
tor fan performance without removing panels or creating air
by-pass of the coils. Condensate pan shall be internally
sloped and conform to ASHRAE 62-89 self-draining stan-
dards. Condensate connection shall be a minimum of 1" I.D.
female and be a ridged mount connection. Unit shall incor-
porate a fixed outdoor air damper with an outdoor air intake
opening covered with a bird screen and a rain hood painted
to match the exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable-
pitch motor pulley. Job site selected (B.H.P.) brake horse-
power shall not exceed the motors nameplate horsepower
rating, plus the service factor. Units shall be designed not to
operate above service factor. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC pres-
sure range. The pressure transducer shall provide a 0 - 5 VDC
output signal to a VAV control board which, in turn shall provide
a 2 - 10 VDC speed reference signal to the VFD. The VAV
control board shall operate using factory-installed Supply
Air, Return Air and Outside Air Temperature Sensors. Units
equipped with VFD’s shall have factory-installed manual
bypass as an option.