York BP 072 Heat Pump User Manual


 
036-21630-001-B-0904
22 Unitary Products Group
TABLE 11: PHYSICAL DATA
MODELS BP 072
EVAPORATOR
BLOWER
Centrifugal Blower (Dia. x Wd. in.) 12 X 10
Fan Motor HP (Belt Drive) 1 1/2
EVAPORATOR
COIL
Rows Deep 4
Fins Per Inch 13
Face Area (Sq. Ft.) 5.1
CONDENSER
FANS
Propeller Dia. (in.) 24
Fan Motor Hp 1/2
Nom. CFM 4500
CONDENSER
COILS
Rows Deep 2
Fins Per Inch 18
Face Area (Sq. Ft.) 17.1
COMPRESSOR
(Qty. Per Unit)
Scroll Type 1
AIR
FILTERS
Quantity Per Unit (15” X 20” X 1” or 2“) 2
Quantity Per Unit (14” X 25” X 1” or 2“) 1
Total Face Area (sq. ft.) 6.6
CHARGE
Refrigerant 22
(lbs./oz.)
12/0
TABLE 12: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE
kW CAP. MULTI-
PLIER
208
208 1.00
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 13: VOLTAGE LIMITATIONS
1
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60
187 253
460-3-60
414 506
575-3-60
518 506
1. Utilization Range “A” in accordance with ARI Standard
110.