York BP 072 Heat Pump User Manual


 
036-21630-001-B-0904
Unitary Products Group 21
TABLE 10: BP 072 ELECTRICAL DATA BELT DRIVE WITH POWERED CONVENIENCE OUTLET
NONE 0.0 41.5 60
2CE04510525
2
4.0 11.1 55.4 70
2CE04510725
2
5.6 15.5 60.9 70
2CE04511025 8.0 22.2 69.3 80
2CE04511525 11.9 33.0 82.8 90
2CE04512025 15.9 44.1 96.7 100
2CE04513025 22.2 61.6 118.5 125
NONE 0.0 41.5 50
2CE04510525
2
5.3 12.7 57.4 70
2CE04510725
2
7.5 18.0 64.1 70
2CE04511025 10.6 25.5 73.4 80
2CE04511525 15.9 38.2 89.3 90
2CE04512025 21.2 51.0 105.2 110
2CE04513025 29.6 71.2 130.5 150
NONE 0.0 19.3 25
2CE04510746
2
6.8 8.2 29.5 35
2CE04511046
2
10.1 12.1 34.5 35
2CE04511546
2
13.6 16.4 39.7 40
2CE04512046
2
19.5 23.5 48.6 50
2CE04513046
2
28.8 34.6 62.6 70
NONE 0.0 15.9 20
2CE04511058 10.6 10.2 28.7 30
2CE04511558 15.9 15.3 35.0 40
2CE04512058 21.2 20.4 41.4 45
2CE04513058 30.4 29.3 52.5 60
Note 1: HACR Type per NEC
Note 2: These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code
(i.e. Chicago), the fuse block accessories shown below are available for field installation.
Model
Tonnage
Voltage
Minimum
Circuit
Ampacity
Amps
Max
Fuse /
BRKR
1
Size
RLA Each LRA Each
ID
Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
OD
Fan
Motor
FLA
Heater
Amps
2.3 5.2 10.0
230-3-60 19.2 146 2.3 5.2 10.0
208-3-60
1.3 2.6 5.0
575-3-60 1.0 2.0 4.0
460-3-60 73
7.1
Fuse Block
2FB04700425
2FB04700546
6
19.2 146
60
8.3
Compressors
0.0
0.0
0.0
0.0