TABLE 3: BP072 COOLING CAPACITIES (6 TON)
RETURN AIR
OUTDOOR AMBIENT TEMPERATURE
85°F 95°F
GROSS
CAP.
1
MBH
INPUT
2
POWER
kW
GROSS SENSIBLE CAPACITY
1
, MBH
GROSS
CAP.
1
MBH
INPUT
2
POWER
kW
GROSS SENSIBLE CAPACITY
1
, MBH
RETURN AIR DRY BULB TEMP. °F RETURN AIR DRY BULB TEMP. °F
CFM
WB
TEMP
°F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
1800
72 76.1 5.26 45.5 39.7 33.8 28.0 22.2 - - 72.6 5.80 43.1 38.0 32.9 27.7 22.6 - -
67 71.2 5.19 57.8 51.9 46.1 40.3 34.4 28.6 22.8 67.0 5.74 55.0 49.9 44.7 39.6 34.5 29.3 24.2
62 66.0 5.13 66.0 62.8 57.0 51.2 45.3 39.5 33.7 60.9 5.67 60.9 59.8 54.7 49.5 44.4 39.3 34.1
57 65.4 5.12 65.4 64.0 58.1 52.3 46.5 40.6 34.8 60.7 5.67 60.7 59.9 54.7 49.6 44.5 39.3 34.2
2100
72 78.9 5.28 49.9 43.4 37.0 30.6 24.2 - - 75.7 5.83 48.2 42.1 36.0 30.0 23.9 - -
67 73.8 5.21 63.3 56.9 50.4 44.0 37.6 31.2 24.8 69.8 5.77 61.2 55.1 49.0 43.0 36.9 30.8 24.8
62 68.3 5.15 68.3 66.8 62.4 56.0 49.6 43.1 36.7 63.4 5.70 63.4 62.9 59.9 53.9 47.8 41.7 35.7
57 67.8 5.14 67.8 67.0 63.6 57.2 50.8 44.4 38.0 63.2 5.70 63.2 62.8 60.0 53.9 47.9 41.8 35.7
2400
72 81.6 5.30 54.2 47.2 40.2 33.2 26.2 - - 78.7 5.86 53.2 46.2 39.2 32.2 25.2 - -
67 76.3 5.23 68.8 61.8 54.8 47.8 40.8 33.8 26.8 72.6 5.80 67.3 60.3 53.3 46.3 39.4 32.4 25.4
62 70.7 5.17 70.7 70.7 67.8 60.8 53.8 46.8 39.8 66.0 5.73 66.0 66.0 65.2 58.2 51.2 44.2 37.2
57 70.1 5.16 70.1 70.1 69.1 62.1 55.1 48.1 41.1 65.7 5.72 65.7 65.7 65.3 58.3 51.3 44.3 37.3
2700
72 83.3 5.31 58.0 50.1 42.1 34.1 26.2 - - 79.6 5.87 56.9 48.9 41.0 33.0 25.0 - -
67 77.9 5.24 73.3 65.3 57.4 49.4 41.4 33.5 25.5 73.4 5.81 70.8 63.7 55.8 47.8 39.8 31.9 23.9
62 72.1 5.18 72.1 72.1 70.7 62.7 54.7 46.8 38.8 66.7 5.74 66.7 66.7 66.3 58.4 50.4 42.4 34.4
57 71.6 5.17 71.6 71.6 71.1 63.1 55.1 47.2 39.2 66.5 5.74 66.5 66.5 66.3 58.3 50.3 42.3 34.4
3000
72 84.9 5.32 61.9 52.9 44.0 35.0 26.1 - - 80.5 5.89 60.6 51.7 42.8 33.8 24.9 - -
67 79.5 5.25 77.8 68.9 59.9 51.0 42.0 33.1 24.2 74.2 5.83 74.2 67.1 58.2 49.3 40.3 31.4 22.4
62 73.6 5.19 73.6 73.6 73.6 64.7 55.7 46.8 37.8 67.5 5.76 67.5 67.5 67.5 58.5 49.6 40.6 31.7
57 73.0 5.18 73.0 73.0 73.0 64.1 55.1 46.2 37.2 67.2 5.76 67.2 67.2 67.2 58.3 49.4 40.4 31.5
RETURN AIR
OUTDOOR AMBIENT TEMPERATURE
105°F 115°F
GROSS
CAP.
1
MBH
INPUT
2
POWER
kW
GROSS SENSIBLE CAPACITY
1
, MBH
GROSS
CAP.
1
MBH
INPUT
2
POWER
kW
GROSS SENSIBLE CAPACITY
1
, MBH
RETURN AIR DRY BULB TEMP. °F RETURN AIR DRY BULB TEMP. °F
CFM
WB
TEMP
°F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
1800
72 67.5 6.47 40.8 35.7 30.6 25.5 20.3 - - 62.3 7.14 38.6 33.4 28.3 23.2 18.0 - -
67 61.4 6.38 52.1 46.9 41.8 36.7 31.5 26.4 21.3 55.8 7.02 49.2 44.0 38.9 33.8 28.6 23.5 18.4
62 56.3 6.33 56.3 55.4 50.3 45.1 40.0 34.9 29.7 51.8 6.98 51.8 51.0 45.9 40.7 35.6 30.5 25.3
57 55.9 6.31 55.9 55.0 49.9 44.8 39.6 34.5 29.4 51.1 6.95 51.1 50.2 45.0 39.9 34.8 29.6 24.5
2100
72 70.8 6.51 46.1 40.1 34.0 27.9 21.9 - - 66.0 7.19 44.1 38.0 32.0 25.9 19.8 - -
67 64.4 6.41 58.5 52.6 46.5 40.4 34.4 28.3 22.2 59.1 7.06 55.7 50.0 43.9 37.9 31.8 25.7 19.7
62 59.1 6.36 59.1 58.7 55.9 49.8 43.7 37.7 31.6 54.8 7.03 54.8 54.4 51.8 45.7 39.7 33.6 27.5
57 58.6 6.34 58.6 58.2 55.4 49.4 43.3 37.3 31.2 54.0 6.99 54.0 53.6 50.9 44.8 38.8 32.7 26.6
2400
72 74.2 6.55 51.4 44.4 37.4 30.4 23.4 - - 69.6 7.23 49.6 42.6 35.6 28.6 21.6 - -
67 67.4 6.45 64.8 58.2 51.2 44.2 37.2 30.2 23.2 62.3 7.11 62.3 56.0 49.0 42.0 35.0 28.0 21.0
62 61.9 6.40 61.9 61.9 61.5 54.5 47.5 40.5 33.5 57.9 7.07 57.9 57.9 57.8 50.8 43.8 36.8 29.8
57 61.4 6.38 61.4 61.4 61.0 54.0 47.0 40.0 33.0 57.0 7.04 57.0 57.0 56.7 49.7 42.7 35.7 28.7
2700
72 74.3 6.56 54.7 46.8 38.8 30.8 22.8 - - 69.1 7.25 52.5 44.6 36.6 28.6 20.7 - -
67 67.6 6.47 66.3 61.0 53.0 45.1 37.1 29.1 21.2 61.8 7.13 61.8 58.3 50.3 42.3 34.4 26.4 18.4
62 62.1 6.42 62.1 62.1 61.9 53.9 45.9 37.9 30.0 57.4 7.09 57.4 57.4 57.4 49.4 41.4 33.5 25.5
57 61.5 6.40 61.5 61.5 61.3 53.4 45.4 37.4 29.5 56.6 7.06 56.6 56.6 56.4 48.5 40.5 32.5 24.6
3000
72 74.5 6.58 58.0 49.1 40.2 31.2 22.3 - - 68.6 7.27 55.4 46.5 37.6 28.6 19.7 - -
67 67.8 6.49 67.8 63.9 54.9 46.0 37.0 28.1 19.1 61.4 7.15 61.4 60.6 51.6 42.7 33.7 24.8 15.8
62 62.2 6.44 62.2 62.2 62.2 53.3 44.3 35.4 26.5 57.0 7.11 57.0 57.0 57.0 48.1 39.1 30.2 21.2
57 61.7 6.42 61.7 61.7 61.7 52.8 43.8 34.9 25.9 56.1 7.08 56.1 56.1 56.1 47.2 38.3 29.3 20.4
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 X kW. Refer to the
appropriate blower performance table for the KW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.