York B6CH 048 Heat Pump User Manual


 
036-21564-002-A-0404
Unitary Products Group 5
COOLING CAPACITIES - 4 TON (BCH048)
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
85 °F95°F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°F
Entering Dry Bulb, °F Entering Dry Bulb, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2000
72 56 4.1 42 36 31 26 - - - 53 4.5 40 35 29 24 - - -
67 53 4.0 48 47 41 36 30 25 - 51 4.4 46 45 41 35 30 24 -
62 49 4.0 49 49 48 44 38 33 28 46 4.3 46 46 45 41 35 30 24
57 49 3.9 49 49 49 44 38 33 28 46 4.3 46 46 46 41 35 30 24
1800
72 55 4.0 40 35 30 25 - - - 53 4.4 38 33 28 23 - - -
67 52 4.0 47 44 39 34 29 24 - 51 4.4 44 44 39 34 29 24 -
62 48 3.9 48 48 47 43 38 33 28 47 4.3 47 47 45 40 36 31 26
57 48 3.9 48 48 48 43 38 33 28 45 4.2 45 45 45 40 35 30 25
1600
72 53 4.0 37 33 28 24 - - - 52 4.4 36 32 27 23 - - -
67 51 4.0 46 42 37 33 28 24 - 50 4.3 44 43 38 34 29 25 -
62 47 3.9 47 47 46 41 37 32 28 45 4.2 45 45 44 40 36 31 27
57 47 3.9 47 47 47 42 38 33 29 44 4.1 44 44 44 40 36 31 27
1400
72 52 4.0 34 30 26 22 - - - 49 4.3 33 29 25 21 - - -
67 49 3.9 42 38 34 30 26 22 - 47 4.2 42 38 34 30 26 22 -
62 46 3.8 46 45 42 38 34 30 26 43 4.1 43 42 40 36 32 28 24
57 45 3.8 45 45 43 39 35 31 27 42 4.1 42 42 40 36 32 28 24
1200
72 50 3.9 31 27 24 20 - - - 47 4.2 29 25 22 18 - - -
67 47 3.9 38 35 31 28 24 21 - 45 4.2 37 34 30 27 23 20 -
62 44 3.8 44 42 39 35 32 28 25 40 4.1 40 39 36 32 29 25 22
57 44 3.7 44 43 39 36 32 29 25 40 4.0 40 39 36 32 29 25 22
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
105 °F115°F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°F
Entering Dry Bulb, °F Entering Dry Bulb, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2000
72 51 4.9 40 35 29 24 - - - 49 5.2 39 34 29 23 - - -
67 46 4.7 42 42 39 34 28 23 - 41 5.0 40 40 37 32 26 21 -
62 43 4.6 43 43 42 37 32 27 21 40 4.9 40 40 39 34 29 23 18
57 43 4.6 43 43 43 38 32 28 22 40 4.8 40 40 40 34 30 24 19
1800
72 50 4.8 38 33 28 23 - - - 47 5.1 37 32 27 22 - - -
67 45 4.7 41 41 37 32 27 22 - 40 4.9 37 36 35 30 25 20 -
62 42 4.6 42 42 41 37 32 27 22 39 4.8 39 39 37 34 29 24 19
57 42 4.5 42 42 42 37 33 27 23 38 4.7 38 38 38 33 30 25 20
1600
72 49 4.8 35 31 26 22 - - - 46 5.1 34 29 25 20 - - -
67 44 4.6 40 40 35 31 26 22 - 39 4.9 36 36 32 28 23 19 -
62 41 4.5 41 41 40 35 32 27 23 37 4.7 37 37 36 33 28 24 19
57 41 4.4 41 41 41 36 32 28 23 37 4.7 37 37 37 34 28 25 20
1400
72 47 4.7 32 28 24 20 - - - 44 5.0 31 27 23 19 - - -
67 42 4.5 38 36 32 28 24 20 - 37 4.8 36 34 30 26 21 17 -
62 39 4.4 39 38 37 33 28 25 20 36 4.7 36 35 34 30 26 22 18
57 39 4.4 39 39 37 33 29 25 21 36 4.6 36 36 34 31 26 23 19
1200
72 44 4.6 28 25 21 18 - - - 42 4.9 28 24 21 17 - - -
67 40 4.5 36 32 29 25 22 18 - 36 4.7 34 31 27 24 20 17 -
62 38 4.4 38 36 34 29 27 22 20 35 4.6 35 34 30 28 24 20 17
57 37 4.3 37 37 34 30 27 23 20 35 4.6 35 35 31 29 24 21 18
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by
3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW.
Refer to the Blower Performance Table for the KW of the supply air blower motor.
ALL SENSIBLE CAPACITY
NOMINAL RATING