Johnson Controls Unitary Products 5
256819-YTG-J-1208
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow
80% 90% Rated CFM 110% 120%
Capacity Factor
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
AVY24B**H21 AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Blower - Diameter x Width 10 x 7 10 x 7 10 x 10 10 x 10
Motor
HP 1/3 1/2 3/4 1
Nominal RPM 1200 1200 1200 1200
Voltage 230
Amps Full Load (230) 2.8 4.3 5.5 7.0
Filter
1
Type DISPOSABLE OR PERMANENT
Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1
Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK
Shipping / Operating Weight (lbs.) 140/134 170/164
AV - 196/185
SV - 194/181
AV - 199/188
SV - 195/184
1.Field supplied.
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Total Motor Amps Minimum Circuit Ampacity
Max. O.C.P.
Amps/Type
1
Minimum Wire
Size A.W.G.
60 Hertz 60 Hertz
208V 230V 208V 230V
AVY24B**H21 3.2 2.8 4.0 3.5 15 14
AVY36C**H21 4.7 4.3 5.9 5.4 15 14
AVY48D**H21 6.1 5.0 7.6 6.9 15 14
SVY48D**N21 6.1 5.0 7.6 6.9 15 14
AVY60D**H21 7.8 7.0 9.7 8.8 15 14
SVY60D**N21 7.8 7.0 9.7 8.8 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.