Subject to change without notice. Printed in U.S.A. 256819-YTG-J-1208
Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 256819-YTG-I-0808
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
TWO-STAGE COOLING WIRING
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER
enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
TYPICAL APPLICATIONS
CONTROL WIRING - Air Handler & New UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
Conventional Application - Not Hot Heat Pump
THERMOSTAT
AIR HANDLER
BOARD
2 - STAGE SCROLL
HEAT PUMP
RR R
GG
Y2
E
W
W
O O
O
X/L X/L X/L
C
C
Y/Y2
Y1
Y1
Y2 OUT
Y2
W2 OUT
W1 OUT
BS
W2
W1
HUM
COM
HUMIDISTAT
*
Y1
UPFLOW DOWNFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT