COOLING CAPACITIES - 5 TON (BCH060)
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
85 °F95°F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°F
Entering Dry Bulb, °F Entering Dry Bulb, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2500
72 68 5.7 51 44 38 31 - - - 67 6.0 51 45 38 31 - - -
67 65 5.6 58 56 50 43 37 30 - 64 5.9 56 56 50 43 37 30 -
62 61 5.6 61 61 59 53 46 39 33 59 5.9 59 59 57 50 44 38 31
57 60 5.5 60 60 59 53 47 40 33 58 5.8 58 58 57 51 44 39 32
2250
72 67 5.6 48 42 36 30 - - - 66 5.9 48 42 36 30 - - -
67 64 5.6 57 54 48 42 36 30 - 63 5.9 55 54 48 42 35 29 -
62 60 5.5 60 60 57 51 45 39 33 57 5.8 57 57 55 50 44 38 32
57 59 5.5 59 59 58 52 46 40 34 57 5.8 57 57 56 50 45 39 33
2000
72 66 5.6 45 40 34 29 - - - 65 5.9 45 40 34 29 - - -
67 63 5.5 56 51 45 40 35 29 - 61 5.9 55 51 45 40 34 29 -
62 59 5.4 59 59 55 50 44 39 33 56 5.8 56 56 54 49 44 38 33
57 58 5.4 58 58 57 52 46 41 36 56 5.7 56 56 55 50 44 39 34
1750
72 64 5.5 42 37 32 27 - - - 62 5.9 43 38 33 28 - - -
67 61 5.5 52 47 42 37 33 28 - 59 5.8 53 48 44 39 34 29 -
62 57 5.4 57 56 51 46 41 37 32 54 5.7 54 54 52 48 43 38 33
57 57 5.4 57 57 53 48 44 39 34 54 5.7 54 54 53 49 43 39 34
1500
72 62 5.5 38 34 30 25 - - - 60 5.8 41 36 32 28 - - -
67 59 5.5 48 43 39 35 31 26 - 57 5.8 51 46 42 38 34 29 -
62 55 5.4 55 52 47 43 39 35 30 52 5.7 52 52 50 46 42 38 34
57 55 5.3 55 54 49 45 41 37 32 52 5.6 52 52 51 47 42 39 35
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
105 °F115°F
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Total
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°F
Entering Dry Bulb, °F Entering Dry Bulb, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
2500
72 64 6.0 51 44 38 31 - - - 60 6.9 50 43 37 30 - - -
67 59 5.9 51 51 49 42 36 29 - 54 6.6 54 53 47 41 34 27 -
62 54 5.9 54 54 51 46 40 33 26 49 6.5 49 49 48 42 35 28 22
57 54 5.8 54 54 52 46 41 33 26 49 6.5 49 49 49 43 35 28 23
2250
72 63 5.9 48 42 36 30 - - - 60 6.8 47 41 35 29 - - -
67 58 5.9 51 51 46 40 34 28 - 54 6.6 47 47 45 39 32 26 -
62 53 5.8 53 53 52 46 40 34 28 49 6.5 49 49 47 42 36 30 24
57 53 5.8 53 53 52 46 41 35 27 49 6.4 49 49 48 43 37 31 25
2000
72 62 5.9 45 39 34 28 - - - 59 6.8 44 38 33 27 - - -
67 57 5.9 51 49 44 38 33 27 - 53 6.5 45 45 42 36 31 26 -
62 52 5.8 52 52 51 46 40 35 30 48 6.4 48 48 46 42 36 31 25
57 52 5.7 52 52 51 46 40 36 31 47 6.4 47 47 46 43 36 32 25
1750
72 60 5.9 41 37 32 27 - - - 56 6.7 40 35 30 25 - - -
67 55 5.8 48 46 41 36 31 26 - 51 6.5 43 43 38 33 29 24 -
62 50 5.7 50 50 48 43 39 34 29 46 6.4 46 46 43 38 33 28 24
57 50 5.7 50 50 48 43 39 34 30 45 6.3 45 45 43 38 33 28 25
1500
72 57 5.8 38 34 30 25 - - - 53 6.6 36 31 27 23 - - -
67 53 5.8 47 43 38 34 30 26 - 48 6.4 41 39 35 30 26 22 -
62 48 5.7 48 48 45 41 37 32 28 44 6.3 44 44 39 35 30 26 22
57 48 5.6 48 48 45 41 38 32 28 43 6.2 43 43 40 36 30 26 23
1
These capacitiesare gross ratings.For net capacity, determinethe KW of thesupply air blowermotor from theBlower Performance Table,multiply this value by
3.415 MBH/ KW todetermine the motor heat,and deduct thisheat from thegross capacity ofthe unit.
2
These ratingsinclude the compressorand the outdoor fanmotors but notthe supply airblower motor. Thetotal outdoor fanmotor power inputis 0.35 KW.
Refer tothe Blower PerformanceTable for the KWof the supplyair blower motor.
ALLSENSIBLE CAPACITY
NOMINALRATING