ELECTRICAL DATA - Basic Unit (Belt-Drive)
MODEL
BCH
POWER SUP
-
PLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN. MAX. RLA LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
19.0
11.9
5.9
4.8
105
85
42
34
1.7
1.7
1.0
1.0
5.3
5.3
3.1
3.1
34.1
21.9
11.5
11.1
50
30
15
15
50
30
15
15
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
25.0
14.7
7.7
6.4
105
130
64
52
2.3
2.3
1.4
1.4
8.6
5.2
2.6
2.0
38.6
25.9
13.6
11.4
60
40
20
15
60
40
20
15
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
32.1
19.3
10.0
7.9
169
123
62
50
2.3
2.3
1.4
1.4
8.6
6.0
3.0
2.4
51.4
32.4
16.9
13.7
80
50
25
20
80
50
25
20
NOTES: 1.Utilization Range “A”in accordance withARI Standard 110.
2. Dualelement, time delaytype.
MODEL
BCH
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
KW STAGES
TOT AL
AMPS
036
208-1-60
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
8.6
4.0
5.6
8.0
11.9
15.9
1
1
1
2
2
19.1
27.1
38.3
57.4
76.6
58.0
67.9
81.9
105.8
129.7
70
80
90
110
150
70
80
90
110
150
230-1-60
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
8.6
5.3
7.5
10.6
15.9
21.2
1
1
1
2
2
22.1
31.2
44.2
66.2
88.3
61.7
73.1
89.3
116.9
144.5
70
80
90
125
150
70
80
90
125
150
208-3-60
2CE04510525*
2CE04510725*
2CE04511025
2CE04511525
2CE04512025
5.3
4.0
5.6
8.0
11.9
15.9
1
1
1
2
2
11.0
15.6
22.1
33.1
44.2
35.7
41.4
49.5
63.3
77.1
40
45
50
70
80
40
45
50
70
80
230-3-60
2CE04510525*
2CE04510725*
2CE04511025
2CE04511525
2CE04512025
5.3
5.3
7.5
10.6
15.9
21.2
1
1
1
2
2
12.7
18.0
25.5
38.2
51.0
37.8
44.4
53.7
69.7
85.6
45
50
60
70
90
45
50
60
70
90
460-3-60
2CE04510746*
2CE04511046*
2CE04511546*
2CE04512046*
3.1
6.8
10.1
13.6
19.5
1
1
1
2
8.2
12.1
16.4
23.5
21.7
26.7
31.9
40.8
25
30
35
45
25
30
35
45
575-3-60
2CE04511058
2CE04511558
2CE04512058
3.1
10.6
15.9
21.2
1
1
1
10.2
15.3
20.4
16.6
23.0
29.4
20
25
30
20
25
30
1
Dual element,time delay type
2
Standard circuitbreakers may beused in Canadaand on applications
over 60amps where theheaters are separatelyfused.
* Theseelectric heaters DONOT includea fuse box. Ifa fuse boxis
required tomeet a localcode ((eg., Chicago), thefollowing fuse
block accessoriesare available forfield installation.
ELECTRICAL DATA - Heat Pump with Supplemental Electric Heat (Belt-Drive)
Electric Heat
Correction
Factors
Nominal Voltage Voltage
KW Cap
Multipier
208 208 1.00
240 230 0.92
480 460 0.92
600 575 0.92
Fuse Block
2FB04700425 208/240 Volts
2FB04700546 460 Volts