York 036-048 Heat Pump User Manual


 
279104-YTG-B-0307
Unitary Products Group 11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. E1RA060S(25,46
INDOOR COIL MODEL NO. G2FD060(S,H)24
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1600 1800 2000
ID DB (°F) 85 80 75 85 80 75 85 80 75
ID WB (°F) 71 67 63 71 67 63 71 67 63
65
T.C. 63.0 61.1 60.7 62.9 60.9 61.1 62.9 60.6 61.4
S.C. 39.6 39.7 40.3 41.6 41.5 42.2 43.7 43.3 44.1
KW 3.71 3.66 3.68 3.71 3.66 3.67 3.71 3.67 3.67
75
T.C. 62.3 59.8 57.9 62.5 60.0 58.5 62.6 60.1 59.0
S.C. 39.6 39.3 39.1 41.8 41.3 41.1 43.9 43.3 43.1
KW 4.20 4.14 4.12 4.21 4.15 4.13 4.21 4.16 4.13
85
T.C. 61.7 58.5 55.1 62.0 59.1 55.9 62.3 59.6 56.6
S.C. 39.6 38.9 38.0 41.9 41.1 40.1 44.2 43.3 42.2
KW 4.70 4.63 4.57 4.71 4.64 4.58 4.72 4.65 4.60
95
T.C. 61.0 57.2 52.3 61.5 58.2 53.3 62.0 59.1 54.2
S.C. 39.6 38.5 36.8 42.0 40.9 39.0 44.4 43.3 41.2
KW 5.19 5.11 5.01 5.21 5.13 5.04 5.22 5.14 5.06
105
T.C. 58.3 53.9 49.1 59.1 54.7 49.9 60.0 55.6 50.7
S.C. 38.5 37.2 35.4 41.0 39.6 37.6 43.6 41.9 39.8
KW 5.78 5.67 5.55 5.80 5.69 5.57 5.82 5.71 5.60
115
T.C. 55.5 50.5 45.9 56.8 51.3 46.5 58.0 52.1 47.1
S.C. 37.4 35.9 34.0 40.1 38.2 36.2 42.7 40.5 38.3
KW 6.36 6.22 6.08 6.39 6.25 6.11 6.41 6.27 6.13
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
MA20DN2,4 FC/MC60D3X 1.00 1.00 1.00
N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00
AHP/SHP60D3X 0.98 0.98 1.02
F2FP060 0.98 0.98 1.02
G1FA060S21,24 1.00 1.00 1.00
G1UA060S21,24 1.00 1.00 1.00
FC/MC/PC/UC60*3X 1.00 1.00 1.00