GOLD CGa Gas-Fired Water Boiler — Boiler Manual
24
Part Number 550-101-009/0107
Failure to PREVENTLOWRETURNWATERTEMPERATURE to the boiler could cause corrosion of
the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of
REGULATINGTHEBOILERRETURN
WATERTEMPERATURE
and the SYSTEMSUPPLYTEMPERATURE (such as provided by an INJEC
TIONPUMPINGCONTROL
).
"OILERRETURNWATERTEMPERATUREWILLBEADEQUATELYCONTROLLEDUSINGTHEMETHODSSHOWN
in this manual provided the SYSTEMSUPPLYTEMPERATURE is RELATIVELYCONSTANT
DO NOT apply the methods of this manual if the system is equipped with an OUTDOOR
RESETCONTROL
Instead, PROVIDECONTROLSANDPIPING which can REGULATETHEBOILERRE
TURNWATERTEMPERATURE
at NOLESSTHAN& regardless of system supply temperature.
#ONTACTYOUR7EIL-C,AINREPRESENTATIVEFORSUGGESTEDPIPINGANDCONTROLMETHODS
Failure to
PREVENTCOLDRETURNWATERTEMPERATURE to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
Piping — low temperature systems (continued)
SYSTEM-bypass piping
method
This piping method (&IGURE, page 25) is called a SYS
TEMBYPASS
because part of the circulator flow bypasses
the system (through valve A). This bypassed hot water
from the boiler outlet mixes with cooler system return
water temperature in order to provide minimum 130°F
RETURNWATERTOTHEBOILER6ALVE
B will most often be
full open, but may need to be slightly closed on some
low pressure drop systems in order to cause enough
flow through valve
A.
&IGURE is an alternative piping method that provides
return water temperature control for boilers installed
on
CONVERTEDGRAVITYSYSTEMS (large water content
or steam systems).
$/./4
apply the piping of &IGURE on RADIANT
HEATINGSYSTEMS
. It provides no method of regulat-
ing the water temperature provided to the system and
could result in excessive water temperature in the radi-
ant tubing.
System-bypass piping as shown in
&IGURE can be used
with either zone valve or circulator zoning. When used
with circulator zoning however, the boiler circulator
(item), must be piped as shown. It cannot be used as
one of the zoning circulators.
$/./4 apply system-bypass piping if the reduced
flow in the system could cause poor heat distribution.
That is, system-bypass piping reduces the flow in the
system and increases the water temperature supplied to
the system. This can cause increased heat from radiators
at the beginning of the system and reduced heat from
radiators near the end of the system.
Valve adjustment
1. Start with valve A fully closed and B fully open.
'RADUALLYOPENVALVE
A while closing valve B until
the temperature at gauge reads at least 130°F at all
times.
6ALVE
A regulates the amount of boiler supply water
MIXEDWITHRETURNWATER6ALVE
Bcauses a pressure
drop in the system needed to balance flow through
valve A and the system.
4. The valve adjustment should be done with the
system at the coldest expected temperature (60°F
for converted gravity systems or high mass radiant
systems).
3d