Weil-McLain 78 Burner User Manual


 
Weil-McLain 78 Boiler For Gas, Light Oil, Gas/Light Oil Fired Burners
Before Installing Boiler
1b
Provide clearances for servicing
around boiler:
Back, for breeching - 30 inches.
Left side, for cleaning and tankless heater
removal - 34 inches
Allow sufficient space on remaining sides
for cleaning, servicing and burner
installation. See burner literature for length.
Clearance from vent pipe to combustible
materials:
- singlewall vent pipe - 18 inches
- doublewall vent pipe - refer to vent pipe
manufacturer’s recommendations for vent
pipe clearances
Lay a foundation, if needed:
Floor construction and condition must be
suitable for weight of boiler when filled with
water. See page 31 for boiler weight/water
weight.
A level concrete or brick foundation is
required when:
A floor could possibly become flooded
Non-level conditions exist
Part No. 550-141-705
4
Boiler Foundation Length Table
Boiler L Boiler L
Model Inches Model Inches
378 23 878 58
478 30 978 65
578 37 1078 72
678 44 1178 79
778 51 1278 86
2" Min.
L
30"
Figure 3 Boiler Foundation