Weil-McLain 550-141-826/1201 Boiler User Manual


 
For P-WGO and A-WGO boiler:
1. Secure universal mounting flange and gasket to
burner mounting door. Use three bolts provided.
2. Secure burner on flange with three bolts.
3. Position burner so end of air tube is level to 1½°
tilt downward. Open door to verify burner position.
End of air tube should be flush to ¼" recessed
from inside wall of burner door refractory. Check
for secure placement of insulation on target wall,
chamber floor and burner mounting door.
Securely close door with nut.
Install Packaged and Non-Packaged Boiler
Install burner (also refer to instructions packed with burner):
Burners designed for use with Weil-McLain 68 boilers must not be used on GOLD Oil
boilers. Contact individual burner manufacturers for GOLD Oil applications.
Water Boiler Controls
FIGURE 5
Relief
Valve
Water
Pressure-Temperature
Gauge
Limit Control
Drain Valve
Circulator
11