Ultimate Products PF Series Boiler User Manual


 
SUGGESTED NOZZLES AND SETTINGS
FOR BECKETT AFG AND CF375 OIL BURNER SERIES
40
NOTE: These settings are intended for
initial start up only. Final adjustment
must be made using combination test
instruments
Pump pressure is set at 140 psig.
All burners fired at +.01 to +.1 inches w.c. draft over fire
*CF375 - Low fire baffle different from AFG
MODEL RATE NOZZLE HEAD-ADJ.
LOW FIRE
BAFFLE
AIR
SHUTTER
AIR
BAND
OIL
BURNER
DPFO-3 .65 .60-80°A F 0 - 1 1/8 Yes 10 1 AFG
.75 .65-70°A F 0 - 1 1/8 No 10 0 AFG
.90 .75-80°B F 3 - 1 1/8 No 10 0 AFG
DPFO-4 .65 .60-80°A F 0 - 1 1/8 Yes 10 1 AFG
.90 .75-80°A F 3 - 1 1/8 No 10 0 AFG
1.35 1.20-80°B F 6 - 1 1/8 No 10 2 AFG
DPFO-5 .75 .65-80°A F 3 - 1 1/8 Yes 10 1 AFG
1.10 1.00-80°A F 6 - 1 1/8 No 10 1 AFG
1.70 1.50-80°A F12 - 1 1/8 No 10 3 AFG
DPFO-7 1.00 .90-80°B F 3 - 1 1/8 No 10 0 AFG
1.60 1.35-80°B F12 - 1 1/8 No 10 1 AFG
2.35 2.00-60°B SV1 - # 3 No 10 2.5 CF375
DPFO-9 1.35 1.20-70°A F 6 - 1 1/8 No 10 2 AFG
2.00 1.65-40°B SV1 - # 1 Yes* 6.5 0 CF375
3.00 2.50-60°B SV1 - # 5 Yes* 10 4 CF375
DPFO-3T .65 .60-80°A F 0 - 1 1/8 Yes 10 2 AFG
.85 .75-80°A F 3 - 1 1/8 No 10 1 AFG
1.10 .90-80°B F 3 - 1 1/8 No 10 1 AFG
DPFO-4T .65 .60-80°B F 0 - 1 1/8 Yes 10 1 AFG
1.00 .85-80°B F 3 - 1 1/8 No 10 1 AFG
1.45 1.25-80°B F 6 - 1 1/8 No 10 2 AFG
DPFO-5T .80 .65-70°A F 3 - 1 1/8 Yes 10 0 AFG
1.20 1.00-70°A F 6 - 1 1/8 No 10 1 AFG
1.75 1.50-70°A F12 - 1 1/8 No 10 3 AFG
DPFO-6T .95 .85-80°B F 3 - 1 1/8 No 10 2 AFG
1.45 1.20-80°B F 6 - 1 1/8 No 10 3 AFG
2.10 1.75-60°B SV1 - # 2 Yes* 10 0 CF375
DPFO-8T 1.25 1.00-70°A F 6 - 1 1/8 No 10 6 AFG
1.90 1.50-60°B SV1 - # 1 Yes* 6 0 CF375
2.75 2.25-60°B SV1 - # 5 Yes* 10 3 CF375