Trion 600M Air Cleaner User Manual


 
5
CAUTION:
When using flex duct connections with other than
straight runs of duct, 45 degree elbows should be used
to connect ducting to flanged collars to maximize air
flow.
ENCLOSED MACHINING CENTER DIRECT MOUNT
1. When mounting directly to an enclosed
machining center ensure there is 53” (135 cm)
clearance above the enclosure and structure
integrity is sufficient to support the MP 600M.
2. Open the filter access door and remove all the
filtering elements. Set these components aside
until the installation is complete.
3. Prepare an outlet opening on the top of he
enclosed machining center (8” minimum to 20”
maximum diameter opening).
4. Center the MP600M over opening and secure to
the enclosure with self-drilling/self-tapping
screws or other similar method in accordance
with local codes. No additional duct connections
or drain plumbing is required on this type of
installation.
ARM ASSEMBLY (OPTIONAL) MOUNTING
Mount the arm assembly(s) to the arm connection collar
on the inlet plenum in accordance with the mounting
instructions provided in the arm assembly kit.
TRAPEZE MOUNT
1. Four (4) through holes are provided in the inlet
plenum bottom flange to which two (2) mounting
channels are affixed with 3/8” hardware (not
provided).
2. The MP600M can be suspended from overhead
with chains or 3/8” diameter (minimum) rods (not
provided).
3. The inlet plenum is equipped with a ½” half
coupler to connect drain piping. Plumbing should
be routed to the collection point to facilitate
drainage (P – trap not Required).
4. Affix duct(s) or elbow fitting(s) or flex hose(s) to
the inlet plenum flange collar using hose clamps
or other similar connection method (not
provided).
MINI-HELIC GAUGE (Optional Mounting)
1. Gauge may be mounted directly on MP600M
unit or may be remotely mounted for improved
visibility.
2. Gauge may be connected to measure entire
system static pressure or only pressure drop
across filter section.
3. All hardware, components and detailed
installation instructions are included in gauge kit
option.
Figure 3 - MP 600M Wall Mounted with 8” Arm Assembly and Drain Pipe