22-1650-13 DATA SUBJECT TO CHANGE WITHOUT NOTICE 15
*UD2C100B9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
AIRFLOW
SETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 7 SW 8 0.1 0.3 0.5 0.7 0.9
HEATING
1ST
STAGE
LOW ON ON
CFM
TEMP. RISE
WATTS
953
50
93
944
50
146
936
51
193
908
52
243
887
54
292
MEDIUM ** ON OFF
CFM
TEMP. RISE
WATTS
1142
42
135
1141
42
200
1135
42
255
1112
43
322
1098
43
377
HIGH OFF OFF
CFM
TEMP. RISE
WATTS
1258
38
169
1260
38
240
1256
38
302
1236
38
378
1227
39
437
HEATING
2ND
STAGE
LOW ON ON
CFM
TEMP. RISE
WATTS
1312
52
188
1317
52
261
1314
52
326
1294
53
406
1287
53
468
MEDIUM ** ON OFF
CFM
TEMP. RISE
WATTS
1577
44
301
1592
43
387
1592
43
468
1597
43
563
1582
43
644
HIGH OFF OFF
CFM
TEMP. RISE
WATTS
1739
39
392
1761
39
486
1762
39
575
1753
39
675
1762
39
774
*UD2C100B9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER
OUTDOOR
UNIT SIZE
(TONS)
AIRFLOW
SETTING
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE
SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9
3.0
LOW
(350 CFM/TON)
ON ON OFF ON
CFM
WATTS
1056
114
1050
173
1044
225
1019
284
1002
336
NORMAL
(400 CFM/TON)
ON ON OFF OFF
CFM
WATTS
1199
151
1199
219
1194
277
1172
349
1161
405
HIGH
(450 CFM/TON)
ON ON ON OFF
CFM
WATTS
1342
198
1348
273
1345
340
1326
422
1320
486
3.5
LOW
(350 CFM/TON)
OFF ON OFF ON
CFM
WATTS
1223
158
1224
227
1219
287
1198
361
1187
418
NORMAL
(400 CFM/TON)
OFF ON OFF OFF
CFM
WATTS
1389
217
1397
294
1395
363
1377
449
1373
515
HIGH
(450 CFM/TON)
OFF ON ON OFF
CFM
WATTS
1556
291
1570
376
1570
455
1556
549
1559
629
4.0
LOW
(350 CFM/TON)
ON OFF OFF ON
CFM
WATTS
1389
217
1397
294
1395
363
1377
449
1373
515
NORMAL
(400 CFM/TON)
ON OFF OFF OFF
CFM
WATTS
1580
303
1595
389
1595
469
1582
565
1585
647
HIGH
(450 CFM/TON)
ON OFF ON OFF
CFM
WATTS
1770
411
1793
507
1795
598
1787
698
1797
801
5.0 **
LOW
(350 CFM/TON)
OFF OFF OFF ON
CFM
WATTS
1723
382
1744
475
1754
564
1735
663
1744
760
NORMAL **
(400 CFM/TON)
OFF OFF OFF OFF
CFM
WATTS
1961
546
1991
652
1996
751
1991
850
2010
981
HIGH
(450 CFM/TON)
OFF OFF ON OFF
CFM
WATTS
2199
754
2217
875
2217
983
2197
1067
1987
943
NOTES:
1. * First letter may be "A" or "T"
2. ** Factory setting
3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.
4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton;
HIGH 450 cfm/ton is for DRY CLIMATE setting